Section IX - Technical data
Quincy Compressor
97
• For AWG8, the maximum current at 40 °C is 50 A x 0.88 = 44 A, which is sufficient
=> use AWG8.
• Install the prescribed maximum fuse (40 A) on each cable
• Parallel supply cable (2 x 3 2 PE - configuration (2)):
• I = (28 A + 25%)/2 = (28 x 1.25)/2 = 17.5 A
• For a AWG14, the maximum current at 40 °C is 20 A x 0.88 x 0.8 = 14.1 A, which is
insufficient. For an AWG14, the maximum current is 25 x 0.88 x 0.8 = 17.6 A.
So 2 parallel cables of 3 x AWG12 + 2 x AWG12 are sufficient.
• Install 20 A fuses on each cable..
Reference conditions and limitations
Reference conditions
Air inlet pressure (absolute)
bar
1
Air inlet pressure (absolute)
psi
14.5
Air inlet temperature
ºC
20
Air inlet temperature
ºF
68
Relative humidity
%
0
Working pressure
See section Compressor data
Limits
Maximum working pressure
See section Compressor data
Maximum inlet temperature
ºC
40
Maximum inlet temperature
ºF
104
Minimum ambient temperature
ºC
0
Minimum ambient temperature
ºF
32