Section III - Controller
70
Quincy Compressor
Compressors with built-in refrigeration dryer
Minimum setting
Factory setting
Maximum setting
Starting pressure
Starting pressure (8 bar com-
pressors)
bar(e)
4
6.8
7.8
Starting pressure (8 bar com-
pressors)
psig
58
98.6
113.1
Starting pressure (10 bar
compressors)
bar(e)
4
8.8
9.8
Starting pressure (10 bar
compressors)
psig
58
127.6
142.1
Minimum setting
Factory setting
Maximum setting
Stopping pressure
Stopping pressure (8 bar
compressors)
bar(e)
4
7.8
7.8
Stopping pressure (8 bar
compressors)
psig
58
113.1
113.1
Stopping pressure (10 bar
compressors)
bar(e)
4
9.8
9.8
Stopping pressure (10 bar
compressors)
psig
58
142.1
142.1
Parameters
Minimum setting
Factory setting
Maximum setting
Allowed number of motor
starts per day
72
720
720
Power recovery time (Auto-
matic restart function)
s
60
60
3600
Restart delay
s
0
0
1200
Communication time-out
s
10
30
60
Protections
Minimum setting
Factory setting
Maximum setting
Ambient temperature warn-
ing level
°C
0
40
40
Ambient temperature warn-
ing level
°F
32
104
104
Ambient temperature shut-
down level
°C
0
45
45
Ambient temperature shut-
down level
°F
32
113
113