12
July 2004
E. Moisture is not draining.
1. Clogged solenoid valve.
2. Defective timer board.
3. Defective solenoid valve.
4. Clogged drain lines.
a. Press the PUSH-TO-TEST switch
several times.
b. Disconnect the drain lines to the
solenoid valve and blow
compressed air from outlet while
pressing the PUSH-TO-TEST
switch.
a. Replace.
a. Replace.
a. Clean or replace.
F. Oil filter not draining. (Oil level
seen above half way point through
the bowl sight glass.)
1. Defective drain valve.
2. Plugged drain valve.
a. Replace.
b. Clean in soap and water or
replace.
Table 1 — Troubleshooting Guide
Symptoms
Cause
Remedy