Network nodes with gateway WTX16.GSM/IP/MOD-1 

10.09.2009 

WTX16.IP 

The WTX16.IP network node features an Ethernet interface, which connects to the outside 
world via an RJ45 connector, where the net-work cable is to be connected.  
The distance to the network conduit box may not exceed 2 meters.  
It is possible, to choose fixed or dynamic (DHCP) IP addresses for WAN communication. 
The transmission in WAN can be done secured by SSL or unsecured.  

Parameter setting 

The WTX16.GSM, WTX16.MOD and WTX16.IP network nodes are parameterized with the 
ACT21 software. The scope of delivery of the software includes an RS-232 cable for con-
necting the PC to the gateway. 

Sealing 

On completion of commissioning, secure the network node with the seal provided. Insert the 
seal in the opening to the right of the network node. 

Safety guidelines 

After opening the housing, certain parts of the device / system that become accessible carry 
dangerous voltage. Only qualified staff may interfere with such devices / sys-tems. 

 

To ensure correct and safe operation, the pro-duct must be adequately shipped, stored, 
installed, operated and maintained. 

 

Staff dealing with the product must be familiar with all potential hazards and maintenan-
ce measures in accordance with the instructions given in this document.  

 

It must be possible to disconnect the device from the power supply at an easily acces-
sible point (e.g. a switch in the power cable)  

 

The connection cable has to be protected by an appropriate fuse. Whenever performing 
any work on the WTX16..., disconnect the device from the mains supply.  

Non-observance of these warning notes can lead to personal injury or damage to 
property!

 

The local regulations for electrical installations and wireless systems must be complied with. 

Pursuant to the "Verordnung über Allgemeine Bedingungen für die Elektrizitätsversorgung 
von Tarifkunden (AVBEltV)" of the Ministry of Economics, electrical installations behind the 
house’s fused connection may only be erected, extended, changed and maintained by elec-
trical installers that are registered with an electric utility. They must ensure that the general 
technical regulations and legal safety regulations are complied with. 

M-Bus connection 

Each network node has a plug terminal for a permanently installed M-Bus connection. A 
fitting plug is included.  

RESET

MODE

permanently connected M-Bus

max. 5 unit loads

temporary

 M-Bus connection

(WTX16.GSM, WTX16.IP:

connection to gateway)

 

In Germany: 

Summary of Contents for WTX16.GSM

Page 1: ...been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building Communication between several net work n...

Page 2: ...ster Max number of meters WTX16 GSM Network node with gateway remote readout via GSM yes 5 additional unit loads 2000 WTX16 IP Network node with gateway remote readout via Ethernet yes 5 additional un...

Page 3: ...ay to store data of up to 2000 meters and to provide a possibility for remote readout via GSM or Ethernet The gateway has an additional M Bus master that can drive up to 5 additional external M Bus un...

Page 4: ...electrical connections are made The electronics section is identical for all types of network nodes It contains control ele ments of the network RESET MODE DISPLAY 1 2 3 4 6 7 11 10 8 9 5 1 Connector...

Page 5: ...y DC 3 6 V 2 Indication of mains supply red LED 3 permanently installed cable no flexible cable 4 SIM card holder WTX16 GSM only 5 RS232 interface for servicing 6 Connector for M bus service connectio...

Page 6: ...red LED 3 permanently installed cable no flexible cable 4 SIM card holder WTX16 MOD only 5 RS232 interface for servicing 6 Connector for M bus service connection 7 Anschluss f r M Bus 8 mains connect...

Page 7: ...It can also be started manually with the ACT26 service tool Installa tionsmode2 In installation mode the radio network will be built up automati cally Metering devices that transmit installation tele...

Page 8: ...The registration of the device takes place and search mode starts Delete from version 2 2 for example If an already registered IrDA capable metering device is connected in IrDA master mode it can be r...

Page 9: ...ss II Then the live L and neutral N conductors must be connected to terminal IN of the power pack Mains voltage must be in the range from AC 100 to 240 V 50 60 Hz There is no protective earth PE conne...

Page 10: ...for voice and data service SIM cards only sold for voice service or M2M service cannot be used For that purpose remove the upper section of the WTX16 GSM from the base Press the SIM card slightly in...

Page 11: ...tained Staff dealing with the product must be familiar with all potential hazards and maintenan ce measures in accordance with the instructions given in this document It must be possible to disconnect...

Page 12: ...cy of transmission 1 Permanent ambient temperature Transport and storage Operation 20 60 C 30 C recommended 0 55 C Weight 0 3 kg Dimensions 184 31 8 9 7 200 6 0 R 1 5 0 R 100 150 250 2 5 0 R 55 250 2...

Reviews: