background image

7/12 

www.qundis.com 

Network nodes with gateway WTX16.GSM/IP/MOD-1 

10.09.2009 

The display of the WT…16… facilitates commissioning work and troubleshooting. In addition 
to the standard display that shows the operating mode of the WTT16, there are 5 different 
display levels from “A“ to “E“ that can be selected by the user. 
Display level 

 

 

Current operating mode 

 

 

WT…16 number (primary address) and alternate 
network number  

 

Number of WT…16 on the network 

 

Number of consumption meters on the network 

 

Remaining capacity of the WTT16’s main battery 
in % 

 

Error code (3 groups) 

There are different operating modes some of which can be selected by pressing the button 
on the network node; some are selected automatically, or from a connected PC via the 
ACT26 commissioning software. The selected operating mode appears on the display: 

Mode Display 

Explanation 

Idle-mode 

Delivery status. Switch to install mode by pressing the but-
ton MODE (>2 sec). 

Standard mode

This is the normal operating mode of the data collectors: 
Telegrams from the metering devices can received, stored 
and handled further by the network. 

Extended stan-
dardmode

1)

 

M

The receiver is always active to ensure fast communication. 
This mode is automatically activated in the case of mains-
powered operation (WTX16...). It can also be started manually 
with the ACT26 service tool. 

Installa-
tionsmode

2)

 

In installation mode, the radio network will be built up automati-
cally. Metering devices that transmit installation telegrams in 
this operating mode will be registered in the network. This 
mode is started by pressing the MODE button (>2sec). 

Extended in-
stalla-
tionsmode

2)

 

M

The extended Installation mode will register all metering 
devices that transmit either installation or data telegrams. 
This mode is useful if network is expanded later.

 

Protected in-
stallations 
mode 

2)3)

 

Same as installation mode, except that connections are built up 
only by devices with the same network signature. 

Search 
mode 

T

his mode restores radio connection to lost or manually 

registered metering devices. This mode starts automatically

.

 

Extended 
search 
mode

2)

 

M

This search run is used to restore the radio connection to lost 
or manually registered metering devices. 
Starting from version 2.2 this mode can also started manually 
by setting jumper 1 (in the plug field) and pressing the MODE 
button ( >2 sec.) 

Delete-mode

2)3)

Same as installation mode, except that all registered me-
tering devices which are transmitting installation telegrams 
will be deleted. (meter replacement) 

1) 

In battery powered network nodes this mode is terminated automatically after eight hours. 

2) 

This mode is terminated automatically after eight hours. 

3) 

Possibly only with the software ACT26 version 2.0 or higher 

Display 

Operating modes 

Summary of Contents for WTX16.GSM

Page 1: ...been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building Communication between several net work n...

Page 2: ...ster Max number of meters WTX16 GSM Network node with gateway remote readout via GSM yes 5 additional unit loads 2000 WTX16 IP Network node with gateway remote readout via Ethernet yes 5 additional un...

Page 3: ...ay to store data of up to 2000 meters and to provide a possibility for remote readout via GSM or Ethernet The gateway has an additional M Bus master that can drive up to 5 additional external M Bus un...

Page 4: ...electrical connections are made The electronics section is identical for all types of network nodes It contains control ele ments of the network RESET MODE DISPLAY 1 2 3 4 6 7 11 10 8 9 5 1 Connector...

Page 5: ...y DC 3 6 V 2 Indication of mains supply red LED 3 permanently installed cable no flexible cable 4 SIM card holder WTX16 GSM only 5 RS232 interface for servicing 6 Connector for M bus service connectio...

Page 6: ...red LED 3 permanently installed cable no flexible cable 4 SIM card holder WTX16 MOD only 5 RS232 interface for servicing 6 Connector for M bus service connection 7 Anschluss f r M Bus 8 mains connect...

Page 7: ...It can also be started manually with the ACT26 service tool Installa tionsmode2 In installation mode the radio network will be built up automati cally Metering devices that transmit installation tele...

Page 8: ...The registration of the device takes place and search mode starts Delete from version 2 2 for example If an already registered IrDA capable metering device is connected in IrDA master mode it can be r...

Page 9: ...ss II Then the live L and neutral N conductors must be connected to terminal IN of the power pack Mains voltage must be in the range from AC 100 to 240 V 50 60 Hz There is no protective earth PE conne...

Page 10: ...for voice and data service SIM cards only sold for voice service or M2M service cannot be used For that purpose remove the upper section of the WTX16 GSM from the base Press the SIM card slightly in...

Page 11: ...tained Staff dealing with the product must be familiar with all potential hazards and maintenan ce measures in accordance with the instructions given in this document It must be possible to disconnect...

Page 12: ...cy of transmission 1 Permanent ambient temperature Transport and storage Operation 20 60 C 30 C recommended 0 55 C Weight 0 3 kg Dimensions 184 31 8 9 7 200 6 0 R 1 5 0 R 100 150 250 2 5 0 R 55 250 2...

Reviews: