Network nodes with gateway WTX16.GSM/IP/MOD-1 

10.09.2009 

S

N

L

R1 ... Rn

M1 M2

 

 
 
 
S switch 
L, N 

AC 230 V mains supply 

M1, M2 

M-Bus output 

R1 ... Rn 

optional interface(s) 

1

2

3

 
 

Mains connection L and N 

Permanently installed mains cable (no flexible 
power cable!) 

Extra insulation (shrink sleeve) 

 

Connect the AC 230 V power supply line to the power pack of the WTX16… in the 
following order: Remove the upper housing section of the WTX16… from the 
base. For that purpose, remove the 2 cable connections (power supply (4) and M-
Bus (6)) between gateway and base. Then, use a suitable tool (screwdriver or 
similar) to slightly open one of the two lateral fixing levers so that upper housing 
section and base can be separated. Then, the top section of the WT…16 is to be 
fitted using 2 dowels and screws (spacing of dowels is 184 mm with the 
WTX16...). 

Connection of the AC 230 V power line to the power pack of the WTX16... is to be made as 
follows: 
A 2-core mains cable (L and N) has to be preinstalled at the mounting site already. The 
power pack must be connected by qualified staff. The cores must be sheathed with the en-
closed insulating sleeves to ensure compliance with safety class II. Then, the live (L) and 
neutral (N) conductors must be connected to terminal “IN” of the power pack. Mains voltage 
must be in the range from AC 100 to 240 V (50 / 60 Hz). There is no protective earth (PE) 
connection. Then, cable strain relief must be provided by fitting cable ties. 
Once the top section of the WTX16 is fitted, the housing with the electronics can be snapped 
on. Then, the power supply connector can be plugged into the electronics section and the 
WTT16 switched to installation mode by pressing the MODE button (red) for a few seconds. 
Then, additional network nodes or consumption meters of the Q AMR system can automati-
cally configure themselves to form a network. 
The standard baud rate of M-Bus master is 2400 Bd. To include 300 Bd M-Bus search it is 
possible to switch this feature by parameterization software ACT21. 
For updating M-bus device directory, there is an automatic search run for new connected 
devices every 28 days. Devices, disconnected from M-bus, will be automatically deleted 
from directory after 7 days. 
After complete installation of all meters and network nodes, the gateway has to do a search 
run to find all devices of network(s).  
The search run started by triggering a command at the connected PC or by remote using the 
software ACS26.  
 

Connection diagram 

 

CAUTION: 
Connect the mains cable to 
the power supply unit only! 

Mains connection 

Search run 

Summary of Contents for WTX16.GSM

Page 1: ...been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building Communication between several net work n...

Page 2: ...ster Max number of meters WTX16 GSM Network node with gateway remote readout via GSM yes 5 additional unit loads 2000 WTX16 IP Network node with gateway remote readout via Ethernet yes 5 additional un...

Page 3: ...ay to store data of up to 2000 meters and to provide a possibility for remote readout via GSM or Ethernet The gateway has an additional M Bus master that can drive up to 5 additional external M Bus un...

Page 4: ...electrical connections are made The electronics section is identical for all types of network nodes It contains control ele ments of the network RESET MODE DISPLAY 1 2 3 4 6 7 11 10 8 9 5 1 Connector...

Page 5: ...y DC 3 6 V 2 Indication of mains supply red LED 3 permanently installed cable no flexible cable 4 SIM card holder WTX16 GSM only 5 RS232 interface for servicing 6 Connector for M bus service connectio...

Page 6: ...red LED 3 permanently installed cable no flexible cable 4 SIM card holder WTX16 MOD only 5 RS232 interface for servicing 6 Connector for M bus service connection 7 Anschluss f r M Bus 8 mains connect...

Page 7: ...It can also be started manually with the ACT26 service tool Installa tionsmode2 In installation mode the radio network will be built up automati cally Metering devices that transmit installation tele...

Page 8: ...The registration of the device takes place and search mode starts Delete from version 2 2 for example If an already registered IrDA capable metering device is connected in IrDA master mode it can be r...

Page 9: ...ss II Then the live L and neutral N conductors must be connected to terminal IN of the power pack Mains voltage must be in the range from AC 100 to 240 V 50 60 Hz There is no protective earth PE conne...

Page 10: ...for voice and data service SIM cards only sold for voice service or M2M service cannot be used For that purpose remove the upper section of the WTX16 GSM from the base Press the SIM card slightly in...

Page 11: ...tained Staff dealing with the product must be familiar with all potential hazards and maintenan ce measures in accordance with the instructions given in this document It must be possible to disconnect...

Page 12: ...cy of transmission 1 Permanent ambient temperature Transport and storage Operation 20 60 C 30 C recommended 0 55 C Weight 0 3 kg Dimensions 184 31 8 9 7 200 6 0 R 1 5 0 R 100 150 250 2 5 0 R 55 250 2...

Reviews: