background image

Page 3 

START-UP PROCEDURE 

OVERVIEW

  

 

 

“There is no substitute for reading and understanding the operating manual however... You can use the 

instructions on this page for a trouble -free start-up”. 

 
 

HOW TO START-UP THE CGC-1e 

 

1)  

Locate a suitable source for power. A “3-wire”, grounded, 15-amp dedicated circuit is recommended. 

 

2)  

Secure the enclosure to a wall using the enclosed mounting “feet”. The CGC-1e requires a vertical orientation for proper 
internal ventilation. If proper ventilation is not provided, the thermostat may not be able to properly control the 
temperature & humidity of the growing area.

 

 

3)  

Plug the CGC-1e into the power source. Do not connect your lights until you have set the “ON and “OFF” times on the        
24-hour timeclock.  

 

4)  

If you are using a PPM-1c CO

2

 sensor, connect it by removing the “jumper-plug” provided with the CGC-1e and 

connecting the PPM-1c quick-disconnect. Plug the PPM-1c into a source of constant 120-volt power. Refer to the PPM-1c 
instructions for information on how to operate the PPM-1c properly.  

       * Note: The pre-wired “jumper plug” must be connected if the PPM-1c is not being used!

 

 

5)  

You can now set the thermostat and de-humistat to the approximate settings you would like to use. A small, inexpensive 
combination thermometer and hygrometer works just fine to “dial in” the exact settings. Just compare the reading on the 
thermometer to what the CGC-1e is set at and adjust as required. 

 

 

6)  

You can now select the Hydro mode you would like to use. Choose between operating the Hydro outlet during the 
“Daytime” only or, 24-hours a day. Move the Hydro mode switch to the appropriate position. Moving the switch to the 
center “OFF” position momentarily will reset the timer.

 

 

7)  

There are 4 timers on the CGC-1e, which are used to control a hydroponics pump and a CO

2

 valve or generator. To fully 

understand the timers that control the CGC-1e, refer to the Timers section of this manual.  Set the Hydro and CO

2

 timers to 

your desired settings before continuing. (Refer to Timers)

 

 

8)  

The 24-hour timeclock can now be set. Push in the trip levers on the front face of the timer dial for the time you want your 
lights to be “ON”. Rotate the dial to the current time to set the timer. 

 

9)  

You can now plug the equipment you will be using into the appropriate receptacles. Remember that the CGC-1e can 
handle a combined load up to 15-amps. A single 1000-watt HID ballast needs over 9-amps alone. Select and size your 
pumps and fans appropriately or use our UPM-1 or MLCs to increase power capacity. 

 

      *Note: We highly suggest NOT plugging in your HID ballast just yet. 

 

10) 

When the “day” cycle begins, the “Lights” indicator will light up to confirm power is going to the (2) light receptacles. If 
you have selected the “Daytime” setting on the Hydro mode, the “Hydro Pumps” indicator will also light up to indicate 
your pump is powered for the amount of time you selected

 

 

11) 

You can manually override the timeclock to switch from “night” to “day” or back to Night by rotating the outer dial of the 
timeclock slowly clockwise. At night, the Lights and CO

2

 are disabled while the thermostat and humistat continue to 

control the temperature and humidity.  

* NOTE: The Hydro outlet will also be disabled if the “Daytime” mode is selected on the Hydro mode switch. 

 

12) 

When all settings have been confirmed, the HID lights or UPMs can be plugged into the “Lights” receptacles. If more than 
1000 watts are to be controlled, use our Universal Power Modules or the MLCs. 

* IMPORTANT: Do not plug in more than 1000 watts worth of lighting into the CGC-1e receptacles.  

 

13) 

Monitor the equipment connected to the CGC-1e to ensure proper operation. Small adjustments are likely to be made until 
you find the right combination of controls. Once you are happy with the settings sit back and enjoy the show!  

 

For more details concerning any of the CGC-1e functions, refer to the appropriate section of this manual. 

 

Summary of Contents for CGC-1e

Page 1: ...arranty All components are warranted by R M Supply against defects in workmanship and materials under normal use for 3 years from the date of purchase The CGC 1e is 100 maintenance free and does not r...

Page 2: ...ller CO2 ON timer Optional PPM 1c quick connect Hydro OFF timer 2 Light outlets CO2 OFF timer Hydro mode selector switch Temperature controller 2 Hydro pump outlets Fuse protected 15 amps 120 volts Co...

Page 3: ...t control the CGC 1e refer to the Timers section of this manual Set the Hydro and CO2 timers to your desired settings before continuing Refer to Timers 8 The 24 hour timeclock can now be set Push in t...

Page 4: ...reatest accuracy provide the CGC 1e with plenty of fresh air The enclosure is designed to allow air to pass over the humidity sensor HUMIDITY CONTROLLER The CGC 1e utilizes a de humistat to control ve...

Page 5: ...t the Hydro and CO2 timers correctly HYDROPONICS TIMERS The Hydroponic outlet can be configured to cycle one of two ways 24 hours a day or during the daytime only Simply moving the Hydro Mode selector...

Page 6: ...t being drawn out of the area by the ventilated hood exhaust fan If sufficient CO2 is provided and the proper level of nutrients and light is available a 35 increase in growth rate is possible However...

Page 7: ...e PPM 1c controller consists of an infrared detector capable of measuring atmospheric CO2 levels from 0 to 5000 PPM The PPM 1c is powered by an 18 vdc to 24vac power supply When it is connected it wil...

Page 8: ...ation to the CGC 1e The PPM 1c is powered by a 18 24volt power supply MASTER LIGHTING CONTROLLER MLCs The MLC 4 and MLC 4a Master Lighting Controllers are the best devices for controlling up to 4 HID...

Page 9: ...ems to be quite high Make sure your area is sealed You may want to install a motorized damper to seal your exhaust fans when they are OFF Even though the CGC 1e operates a standard timed release seque...

Page 10: ...lbs Relay operations Minimum 100 000 electrical 10 000 000 mechanical MAINTENANCE 1 Consult the troubleshooting chart for a listing of the most common problems 2 DO NOT open the enclosure There are no...

Reviews: