FDV451 / MQFDV453 General Venting Information
This gas appliance is approved to be vented either through the side wall or vertically through the roof.
Only Kingsman
Flex (Z-Flex) Venting Kits and components specifically approved and LABELED for this stove may be used.
This
appliance is also approved for use Simpson-Duravent Direct Vent system (Model DV-GS Series), BDM Pro Form Direct
Vent, Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
Rigid or Hard Pipe
When using Simpson Duravent, Ameri-Vent pipe, BDM Pro Form Direct Vent, ICC Excel Direct, Metal Fab Sure-Seal DV
and or Selkirk Direct Temp a Duravent hard pipe adapter must be used (part # ZDVDFA for fire- places and part #
ZDVDKA for Stoves, Serenity and ZDV3624B). Follow installation instructions provided by Simpson Duravent/Ameri-
Vent/Selkirk Direct Temp, ICC Excel Direct, and Metal Fab Sure-Seal DV for installation of pipe and adhere to the
clearance to combustibles provided in this manual. Apply a bead of Mill Pac high temp sealant to all joints of pipes,
adapters and termination, when using Kingsman Flex (Z-Flex) venting and Simpson Duravent venting.
Flex Pipe Venting
Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the lengths. Pipe can be expanded to
twice their lengths e.g. 4ft. to 8ft. Fully expand pipe and cut off excess.
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an installation attaching at the
fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 4” flex in the center of 7” flex. When forming
bends place spring in bend or before and after. (See Fig. 1). Horizontal runs require support metal straps every 2 feet. In
offset installation support straps should be used to stabilize pipe.
Expand 4” and 7” flex pipe to the point that the 7” protrudes approximately 2 to 3 inches past outer wall and the 4” flex
protrudes approximately 2 to 3 inch
es past the 7” flex. (See Fig. 1). Attach the 4” pipe to the termination first and secure
with sealant and screws then attach the 7” flex to the termination with caulking and screws. Termination may then be
moved back to the outer wall and attached to home screwing into the framing. Silicone around termination to waterproof. If
siding shield is going to be used attach this using same attaching hole as the top of termination after termination has been
caulked for water proofing.
Use Hi Temp Sealant
Apply a bead of Mill Pac high temp sealant to all joints and use four screws to secure each pipe at fireplace, termination
and any joint if joining any sections of pipe.
REMEMBER THAT A 1/4" VERTICAL RISE IS REQUIRED FOR EVERY 12" OF HORIZONTAL RUN
.
⚠
WARNING:
DO NOT mix parts from different systems unless stated in the manual.
NOTE:
It is critical to the proper and safe
operation of this fireplace that on all
connections the inner liner and the outer casing
are both caulked with liberal amounts of
sealant. Do not use any kind of tape or silicone
other than that recommended in this manu
al, Mill
Pac Sealant.
Figure 1
Seal with high temp sealant.
Secure with [4] screws per pipe joint.
Seal with high temp sealant.
Secure with [4] screws per pipe joint.
Clamps Optional
Maximum 2ft distance between
spring spacers.
59
Summary of Contents for Kingsman FDV451LP
Page 42: ...Gas Conversion for Modulator PART C 42...
Page 47: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 47...
Page 48: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 48...
Page 55: ...Proflame 2 Remote Control 55...
Page 57: ...57...