Approved for Power Vent PVH58
The PVH58 Horizontal Power Vent is approved for the following models only:
MDV31, MDV39, MQRB3632, ZDV3622, MQZDV3622, ZDVRB3622, HBZDV3624, HBZDV3628, HBZDV3632,
MQHBZDV3636, HBZDV4224, HBZDV4228, HBZDV4232, MQHBZDV4236, HBZDV4740, MQHBZDV4736,
MQRB4436, MQRB5143, MQRB6961, ZRB46, ZCV3622, ZCVRB3622, ZCV39, ZCV42, MCVP42, MCVST42,
MQZDV3927*, MQZDV4634*, MQZCV48, VRB46
*NOTE: For MQZDV3927 and MQZDV4634, Power Vent Control Module (PVCM) must be placed outside of
Fireplace.
The PVH58 Horizontal Power Vent Termination is intended for use where standard venting
configurations are not possible.
NOTE:
MODELS EQUIPPPED WITH MILLIVOLT/ STANDING PILOT IGNITION: Downward vertical vent runs are
NOT
permitted.
NOTE:
MODELS EQUIPPPED WITH INTERMITTENT PILOT IGNITION:
Downward vertical vent runs are permitted, however, Cold Climate Switch (Standing Pilot Mode) must not be used.
Refer to your appliance manual for Minimum Vertical Rise before First 90° elbow (Measured from bottom of appliance to
center of vent pipe) to avoid overheating of vent pipe.
Refer to PVH58 Manual for proper installation and use.
PVH-58 Maximum / Minimum Vent Lengths:
Maximum
Vent Length is 125 ft plus six 90° elbows with Air Intake Shutter fully closed. Termination
must not be below unit.
This power vent can be installed up to 3ft below the installed fireplace on runs less than 100ft and not
more than four 90° elbows.
Minimum
Vent Length is 3ft horizontal plus minimum vertical rise with Air Intake Shutter fully open.
73