background image

 

 

R.E.

 

Williams

 

Contractor

 

Inc.

        

 

             

www.rewci.com

 

 

Operations Check 

You should familiarize yourself with the operation of the lock and check that all parts work properly. 

 

Remove the battery cover from the back plate and install the 4 x AA cells. 

 

Connect the cables from the front plate and back plate. A bleep should be heard when you do this. If no bleep is 
heard then check that the batteries are correctly installed. 

 

Place the long spindle in the front plate socket and using finger grip only, test that the spindle is easily moved 80 
degrees in both directions. Leave socket in the centered position. 

 

Enter the factory Master Code - Badge Bar 1234. Please Note: When the Master Code is entered 3 times 
consecutively without performing a programming function, a penalty time of 10 seconds is activated. 

 

The Blue light should flash and the spindle should not turn as before. 

 

After 5 seconds the Red light should flash and the spindle should turn easily again. This confirms that the clutch 
engaged correctly when the code was entered. 

 

Disconnect the cables. 

 

Turn the key in the front plate cylinder 90 degrees clockwise and confirm that the spindle will not turn easily with 
the key in this position. Remove the key and confirm that the spindle again turns easily. This confirms that the key 
bypass function operates correctly.  
 
  

Special Fixing Note 
  

Remote Release Option  
Cables are provided for the REM 1 and REM 2 terminals on 
the circuit board. 

REM 1

 is for connection to a Reception Desk push button or 

a Door Intercom system. Pressing the button will cause the 
Blue light to Flash on the lock and release the lock for the 
pre-set time. 

REM 2

 is for connection to a Fire Alarm System so as to 

release a door in an emergency. This allows rooms, wards, 
offices to be easily checked to ensure that no person is 
trapped or overlooked during an emergency or a practice 
fire drill. When activated REM 2 will maintain the unlocked 
condition for 30 minutes, and the Red LED will flash and 
BLEEP during this time. The lock will automatically lock 
again after 30 minutes. If necessary Program 11 can be 
used to re-lock before the end of the 30 minutes. 

REM 1 and REM 2 do not require additional power. They 
are normally open contacts requiring a momentary or 
maintained signal to close.   
 
  

  