Operations Check
You should familiarize yourself with the operation of the lock and check that all parts work properly.
Remove the battery cover from the back plate and install the 4 x AA cells.
Connect the cables from the front plate and back plate. A bleep should be heard when you do this. If no bleep is
heard then check that the batteries are correctly installed.
Place the long spindle in the front plate socket and using finger grip only, test that the spindle is easily moved 80
degrees in both directions. Leave socket in the centered position.
Enter the factory Master Code - Badge Bar 1234. Please Note: When the Master Code is entered 3 times
consecutively without performing a programming function, a penalty time of 10 seconds is activated.
The Blue light should flash and the spindle should not turn as before.
After 5 seconds the Red light should flash and the spindle should turn easily again. This confirms that the clutch
engaged correctly when the code was entered.
Disconnect the cables.
Turn the key in the front plate cylinder 90 degrees clockwise and confirm that the spindle will not turn easily with
the key in this position. Remove the key and confirm that the spindle again turns easily. This confirms that the key
bypass function operates correctly.
Special Fixing Note
Remote Release Option
Cables are provided for the REM 1 and REM 2 terminals on
the circuit board.
REM 1
is for connection to a Reception Desk push button or
a Door Intercom system. Pressing the button will cause the
Blue light to Flash on the lock and release the lock for the
pre-set time.
REM 2
is for connection to a Fire Alarm System so as to
release a door in an emergency. This allows rooms, wards,
offices to be easily checked to ensure that no person is
trapped or overlooked during an emergency or a practice
fire drill. When activated REM 2 will maintain the unlocked
condition for 30 minutes, and the Red LED will flash and
BLEEP during this time. The lock will automatically lock
again after 30 minutes. If necessary Program 11 can be
used to re-lock before the end of the 30 minutes.
REM 1 and REM 2 do not require additional power. They
are normally open contacts requiring a momentary or
maintained signal to close.