This product is intended to be installed only in a restricted access location.
■
This product is intended to be connected to a DC power source that can be
classified as a secondary circuit in accordance with applicable National
requirements for Information Technology Equipment. Generally, these
requirements are based on the International Standard for Safety of for
Information Technology Equipment, IEC 60950-1.
■
This product must be connected to a power distribution device that provides a
means for disconnecting power from the branch supply circuit. The power
distribution device must be provided with an over-current protective device
suitable for interrupting fault currents available from the main source.
■
The rack must be connected to site ground.
■
Ground cable assemblies for enclosures in the racks must be connected to the
cabinet grounding rail. Do not rely on the rack or cabinet chassis to provide
adequate ground/earth continuity.
■
Never connect cables to a terminal when there is power supplied to that circuit.
Cabling requirements
■
Keep power and interface cables clear of foot traffic. Route cables in locations
that protect the cables from damage.
■
Route interface cables away from motors and other sources of magnetic or radio
frequency interference.
■
Stay within the cable length limitations.
■
This product is suitable for installation in Network Telecommunication Facilities
and locations where the NEC applies. The N2S2A is not suitable for Outside
Plant (OSP) installations