FXLED INSTALLATION INSTRUCTIONS
®
GUARD OR SHIELD INSTALLATION
Wire Guard and Poly Shield mount with (4) #8-32
Stainless
Steel Screws.
Screws are provided with the accessory. See
fig. 3 for Guard. See fig. 4 for Shield
1.
Line up guard or shield with existing pre-drilled holes in
frame as shown, tighten screws.
GUARD & SHIELD INSTALLATION
The Wire Guard and Poly Shield can be mounted on the
same fixture with (4) #8-32 screws as shown below.
Stainless
Steel
Screws
Fig. 3
Fig. 4
Note: These instructions do not cover all details or variations
in equipment nor do they provide for every possible situation
during installation, operation or maintenance.
Patent -
US:
pat. D659,280
ON-OFF WIRING
Universal voltage driver permits operation at 120V thru 277V,
50 or 60 Hz. Units ordered with (/480V) suffix are 480V, 60Hz.
For Non-Dimming, follow the wiring directions as in fig. 1.
1.
Connect the black fixture lead to the (+) LINE supply lead.
2.
Connect the white fixture lead to the (-) COMMON supply
lead.
3.
Connect the GROUND wire from fixture to supply ground.
LIGHT
FIXTURE
(+)LINE
BLACK
(-)COMMON
WHITE
GROUND
GROUND
Fig. 1
Fig. 2
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V,
50 or 60 Hz. For 0-10V Dimming, follow the wiring directions
as in fig. 2.
1.
Connect the black fixture lead to the (+) LINE supply lead.
2.
Connect the white fixture lead to the (-) COMMON supply
lead.
3.
Connect the GROUND wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to
the output.
4.
Connect the purple fixture lead to the (V+) DIM lead.
5.
Connect the gray fixture lead to the (V-) DIM lead.
6.
Cap the yellow fixture lead, if present. Do NOT connect.