Wiring
SWITCHED NEUTRAL
The “Switched Neutral” white with red stripe wire is the
neutral line for the load being switched. This enables power
measurement. See the Power Measurement section under
“Functionality” for more information.
BLACK
WHITE/RED
0-10V
DIMMING
Panel
Load
BL
AC
K /
H
O
T
W
H
IT
E /
N
EU
TR
A
L
WHITE
BLACK
RED
WHITE
PURPLE
GRAY
PUR
PL
E
G
R
AY
Setup & Installation
1
Find a suitable location
Use these guidelines when installing devices:
• If there is a clear line of sight between two Lightcloud devices,
they can be placed up to 1000 feet apart.
• If the two devices are separated by ordinary drywall construction,
try to keep them within 100 feet of each other.
• Brick, concrete and steel construction may require additional
Lightcloud devices to go around the obstruction.
!
This product should only be installed by a qualified electrician
and in compliance with local and national electrical codes.
Lightcloud
Gateway
<= 100 ft.
Add an additional Lightcloud
Device to extend network range
around corners
BRICK ,
CONCRETE OR
METAL WALL
DRY WALL
OR SIMIL AR