16.4 Menu 9.7.1 - Setting the heating mode
2.1
Heating mode [ 2 ] - Setting the room temperature controller
with limiter.
2.2
Select and confirm the heating mode
[ 2 ]
.
2.3
Set and confirm the limiting value for
the minimum floor temperature.
Setting range = 10°C to 30 °C
Factory setting = OFF
The setting is undertaken in steps of
1.0 °C.
2.4
Set and confirm the limiting value for
the maximum floor temperature.
Setting range = 20°C to 40 °C
Factory setting = 35 °C
The setting is undertaken in steps of
1.0 °C.
i
If both a minimum and maximum temperature
limit are set, the limiting values must be at least
5 °C apart.
◆
An incorrect setting is automatically corrected by
the controller.