16.2 Troubleshootin
g
Flow Chart (Multiburner)
Refer to control panel
IOS manual for troubleshooting.
Fan motor may have to
be replaced.
Remove obstruction.
No
No
Ye
s
Ye
s
No
No
No
Ye
s
No
No
Ye
s
Ye
s
Ye
s
Ye
s
No
No
Ye
s
No
Ye
s
Ye
s
No
No
No
Ye
s
Check thermostat
and replace if necessar
y.
Turn up thermostat. Does the fan turn on?
Remove obstruction.
Repair
, replace or
tighten hoses as necessar
y.
Is the flue pipe or
the inlet of the
burner obstructed?
Are the hoses to the pressure switch secure and leak free?
Remove Black and Y
ellow
leads from the pressure switch; place a jumper between leads.
Is there a spark?
Replace pressure switch.
Is the igniter gap
set at 3 mm?
Carefully reset gap
to 3 mm.
Replace automatic
control unit.
Unplug burner and check electrode and ignition wire.
Are they damaged?
Replace electrode and ignition wire as needed.
After 20 second pre-purge Is there spark at the igniter?
Check clock program.
Reset as required.
Is there power (230V) to the control panel?
Is the clock set to on?
Is there power output
to the fan?
Disconnect power to the
motor
. Does the
motor turn freely?
Motor may have have tripped
overload switch. W
ait
10 - 15 minutes for
automatic reset.
Is the motor connected
properly? Refer to the wiring diagrams on the motor and in the installation manual.
Is there an obstruction to
the pump impeller?
Summary of Contents for BH15UT
Page 2: ......
Page 4: ......
Page 6: ......
Page 33: ...SECTION 7 U TUBE HEATER INSTALLATION 27 Figure 23 U Tube Assembly Overview mm 200...
Page 55: ...SECTION 10 OPTIONAL HEATER ACCESSORIES 49 Figure 28 U Tube Angle Mounted Figure 29 Linear...
Page 71: ...SECTION 16 TROUBLESHOOTING 65 Troubleshooting Flow Chart Linear Double Linear and U Tube...
Page 73: ...SECTION 16 TROUBLESHOOTING 67 Troubleshooting Flow Chart Multiburner...
Page 81: ......