CLEARANCES TO COMBUSTIBLES (in inches)
FIRE HAZARD.
Always maintain published clearances to combustibles.
In locations used for the storage of combustible materials, signs must be
posted. Consult manual for additional guidelines.
MODEL NO.
SIDE(S)
HL2-DS-30-65/
HL2-DS-30-80
0°
30°
0°
30°
6
9
25
45
25
10
12
12
77
64
ENDS
12
12
TOP
6
9
BEHIND
25
10
FRONT
25
36
END VIEW
0° Mounting
SIDE VIEW
END VIEW
30° Mounting
* Heaters mounted on an angle between 0° and
30° must maintain clearances posted for 0° or
30°, whichever is greater.
** This heater must be installed at least 79” above
the floor/ground level (as applicable).
End
End
BELOW**
60
47
Max.
30˚ Angle
Top
Top
Front
Side
Side
Below
Below
Back
LLTCL018-5c-12/17 (CDS)
MOUNTING ANGLE*
HL2-DS-30-100
This heater must be installed in accordance with the manufacturer’s
instruction and local codes, if any. In absence of local codes, follow the
latest edition of the National Fuel Gas Code, NFPA 54 (ANSI Z223.1) or
the CAN/CCA B149 installation codes.
Hot while in operation.
DO NOT
Touch. Keep children, clothing, and
combustible materials away.
DO NOT
store combustible materials under
this heater while in operation.
Keep burner and control compartment clean. See installation and
operating instructions accompanying heater.
APPLICATION:
Minimum mounting height 79” above finished floor.
If this appliance is installed in one or more of the following locations, then the installation
must be in accordance with the latest edition of the applicable standard(s):
• Aircraft Hangers - ANSI / NFPA 409
• Parking Structure - ANSI / NFPA 88A
• Repair Garages - ANSI / NFPA 88B
LLTCL016a-1x-05/17 (CDS)
SAMPLE
WARNING
!
Read and understand all safety information and warnings in this manual before
installation, operation, and maintenance of the radiant tube heater system.
CLEARANCES TO COMBUSTIBLES (in inches)
FIRE HAZARD.
Always maintain published clearances to combustibles.
In locations used for the storage of combustible materials, signs must be
posted. Consult manual for additional guidelines.
MODEL NO.
SIDE(S)
HL2-DS-30-65/
HL2-DS-30-80
0°
30°
0°
30°
6
9
25
45
25
10
12
12
77
64
ENDS
12
12
TOP
6
9
BEHIND
25
10
FRONT
25
36
END VIEW
0° Mounting
SIDE VIEW
END VIEW
30° Mounting
* Heaters mounted on an angle between 1° and
30° must maintain clearances posted for 0° or
30°; whichever is greater.
** This heater must be installed at least 79” above
the floor/ground level (as applicable).
End
End
BELOW**
60
47
Max.
30˚ Angle
Top
Top
Front
Side
Side
Below
Below
Back
LLTCL016b-1M-08/17 (CDS)
MOUNTING ANGLE*
HL2-DS-30-100
This heater must be installed in accordance with the manufacturer’s
instruction and local codes, if any. In absence of local codes, follow the
latest edition of the National Fuel Gas Code, NFPA 54 (ANSI Z223.1) or
the CAN/CCA B149 installation codes.
Hot while in operation.
DO NOT
Touch. Keep children, clothing, and
combustible materials away.
DO NOT
store combustible materials under
this heater while in operation.
Keep burner and control compartment clean. See installation and
operating instructions accompanying heater.
APPLICATION:
Minimum mounting height 79” above finished floor.
If this appliance is installed in one or more of the following locations, then the installation
must be in accordance with the latest edition of the applicable standard(s):
• Aircraft Hangers - ANSI / NFPA 409
• Parking Structure - ANSI / NFPA 88A
• Repair Garages - ANSI / NFPA 88B
LLTCL016a-1x-05/17 (CDS)
HL2-40-125N
Data on this label is for the model shown on this label. If your heater has been converted,
this information is not accurate. Please contact the factory for assistance.
BURNER COMPONENTS:
For parts replacement information, contact factory at 586-756-0950 or visit www.drp-co.com/parts.
Serial No.: 0914XXXXXXXXXX 0001
Gas Valve:
Circuit Board:
Wire Harness:
N.O. Switch:
N.O. VL Orifice:
N.C. Switch:
N.C. VL Orifice:
Diff Switch:
Diff VL Orifice:
Igniter:
Burner:
16” Tube:
Ind. Lights:
Diag. Light:
Term. Block:
Transformer:
Fan:
Alt. Fan:
Alt. Fan Usage:
Relay:
Filter:
24 Volt In:
120 Volt In:
Gas In:
Extra VL Orifice:
Production Code:
Version:
Stock:
Add-On:
Internal Use Only:
HEATER
TYPE:
Electric:
Tag:
Special 1:
Special 2:
Gas:
Air:
C1
C1
C2 C3
None
N/A
HL2-125
9.14
36E96-224-N
Micro60-24
3 PCS Harness
None
None
None
None
IS22010051F5169
Grey (+ / -)
Norton
Low-Mid
4” Gen.
Yellow - 120V
(Specify TP-#’s)
840
851
852
N/A
N/A
264E
50
3072
380
828
On Circuit Board
None
40 VA
Fasco Lg.
50Hz - 120V
When Specified
None
None
3 T-plug
2 x 4 Box
7/8” FC Flare
None
N/A
826
55A
55B
N/A
N/A
832
66
83
3
1 1/2”
TP-204#
TP-44#
3
1 5/8”
LLWT038
None
3
1 5/8”
Micro60
Plug-Wh.
Orifice Type:
DETROIT RADIANT PRODUCTS COMPANY
21400 HOOVER ROAD - WARREN, MI 48089
(586) 756-0950 www.reverberray.com
LOW-INTENSITY INFRARED HEATER
MAX. HEAT INPUT
MAX. DEBIT CALORIFIQUE
MIN. HEAT INPUT
MIN. DEBIT CALORIFIQUE
VENT CATEGORY
ÉVENT CATÉGORIE
BTU/h
BTU/h
VOLTAGE
AMPS
PHASE
FREQUENCY
Hz
VAC
112671
MANIFOLD PRESSURE
PRESSION A LA TUBULURE D'ALIMENTATION
MAXIMUM INLET PRESSURE
PRESSION D'ALIMENTATION MAXIMALE
MINIMUM INLET PRESSURE FOR PURPOSE OF ADJ.
PRESSION D'ALIMENTATION EN GAS MIN. ADMISE
INCHES W.C.
INCHES W.C.
INCHES W.C.
RADIATEUR À INFRAROUGE À FAIBLE INTENSITÉ
ORIFICE SIZE
DIM DE L'INJECTEUR
THIS DESIGN COMPLIES WITH STANDARD(S):
COMPLES DE CETTE CONCEPTION AVEC LA NORME:
HEATER BUILD TYPE
TYPE OF GAS
TYPE DE GAZ
MIN. MOUNTING ANGLE
MIN. ANGLE DE SUPPORT
MAX. MOUNTING ANGLE
MAX. ANGLE DE SUPPORT
MODEL NUMBER
NUMÉRO DE MODÈLE
SERIAL NUMBER
NUMÉRO DE SÉRIE
VERSION
FOR U.S.A. THIS HEATER IS APPROVED FOR ALTITUDES OF 0-2000 FT.
IN CANADA FOR ALTITUDES OF 4-4500 FT (0-1,370M) ABOVE SEA LEVEL
AU CANADA POUR ALTITUDE DE 0 A 4500 PIEDS (0-0,370M) D’ALTITUDE
FOR OUTDOOR USE ONLY
MADE IN U.S.A.
80,000
52,000
CATEGORY I
1.2
SINGLE
60
120
3.5
14.0
5.0
22
D.M.S.
C1
NATURAL
ANSI Z83.20-2016 • CSA 2.34-2016 Low-Intensity Infrared Heater
0°
30°
HL2-DS-30-80N
YYMMREPCSHIPPE#### 09/17
Detroit Radiant Products Company
21400 Hoover Road Warren MI 48089
(586) 756-0950 www.reverberray.com
LOW-INTENSITY INFRARED HEATER
MAX. HEAT INPUT
MAX. DEBIT CALORIFIQUE
MIN. HEAT INPUT
MIN. DEBIT CALORIFIQUE
VENT CATEGORY
ÉVENT CATÉGORIE
BTU/h
BTU/h
VOLTAGE
AMPS
PHASE
FREQUENCY
Hz
VAC
MANIFOLD PRESSURE
PRESSION A LA TUBULURE D'ALIMENTATION
MAXIMUM INLET PRESSURE
PRESSION D'ALIMENTATION MAXIMALE
MINIMUM INLET PRESSURE FOR PURPOSE OF ADJ.
PRESSION D'ALIMENTATION EN GAS MIN. ADMISE
INCHES W.C.
INCHES W.C.
INCHES W.C.
RADIATEUR À INFRAROUGE À FAIBLE INTENSITÉ
ORIFICE SIZE
DIM DE L'INJECTEUR
THIS DESIGN COMPLIES WITH STANDARD(S):
COMPLES DE CETTE CONCEPTION AVEC LA NORME:
HEATER BUILD TYPE
TYPE OF GAS
TYPE DE GAZ
MIN. MOUNTING ANGLE
MIN. ANGLE DE SUPPORT
MAX. MOUNTING ANGLE
MAX. ANGLE DE SUPPORT
MODEL NUMBER
NUMÉRO DE MODÈLE
SERIAL NUMBER
NUMÉRO DE SÉRIE
VERSION
COMBUSTION CHAMBER
THIS HEATER IS TO BE UN-VENTED ONLY
FOR OUTDOOR USE ONLY.
MADE IN U.S.A.
80,000
52,000
N/A - UNVENTED
4.8
SINGLE
60
120
3.5
14.0
5.0
18
D.M.S.
ANSI Z83.20-2016 • CSA2.34-2016 RADIANT TUBE HEATER
C1
NATURAL
0°
30°
HL2-DS-30-80N
YYMMREPCSHIPPE####
09/17
TP-877
112671
SAMPLE
HL2-DS-30-80N
4
HL2-DS
Series
1.0
Introduction
•
Safety Labels and Their Locations
Back Panel
Top Panel
Bottom Panel
Rating Plate
F/N: LLTB018 (Natural Gas)
F/N: LLTB019 (Propane Gas)
F/N: LLTCL018
Clearances to Combustibles Label
F/N: LLTCL016a
Safety Label
F/N: LLLOGO032
Burner Control Box
Component Label
(located
under the top panel)
Product safety signs or labels should be replaced by the product user when they no longer are legible.
Contact either your local distributor or the product manufacturer for obtaining replacement signs or
labels.
Safety Labels and Their Locations