2. FIRST START-UP
SUPPOR
T CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P27
ACTIVATION PERCENTAGE OF THE SECONDARY UNIT
60 - 100
THE VALUE IS EXPRESSED IN
PERCENTAGE
(PRE-SET BY DEFAULT TO 85%)
P28
DEACTIVATION PERCENTAGE OF THE SECONDARY UNIT
5 - 40
THE VALUE IS EXPRESSED IN
PERCENTAGE
(PRE-SET BY DEFAULT TO 10 %)
P29
ENABLING THE MASTER BOARD WITH CRAD AREA MANAGEMENT
BOARD
0 - 2
0 = DISABLED (PRE-SET BY
DEFAULT)
1 = CRAD AREA BOARD
CONNECTED
2 = CRAD AREA BOARD
CON REMOTE
P30
SETTING THE TEMPERATURE MEASUREMENT UNIT
THROUGH THIS PARAMETER, YOU CAN SELECT THE
MEASUREMENT UNIT OF THE DISPLAYED TEMPERATURE:
CELSIUS (°C) OR FAHRENHEIT (°F) DEGREES.
0 - 1
0 = °C
1 = °F
P31
SELECTION OF THE COUNTRY OF DESTINATION
BY CHANGING THIS PARAMETER, THE CONTROL PARAMETERS
OF THE COMBUSTION ARE AUTOMATICALLY CONFIGURED
ACCORDING TO THE VALUES PRE-SET IN THE COUNTRY OF
DESTINATION OF THE PRODUCT.
0 - 1
0 = OTHER COUNTRY
1 = U.S.A. / CANADA
P32
DOMESTIC CIRCUIT OPERATING MODE
(ONLY FOR THE VERSION WITH REMOTE BOILER SUPPLY
SYSTEM)
0 - 2
0 = DOMESTIC CIRCUIT BY MEANS
OF BOILER PROBE
1 = DOMESTIC CIRCUIT BY MEANS
OF THERMOSTAT
2 =
DOMESTIC CIRCUIT BY MEANS
OF
MODBUS