R1K 34 /B - RAD - ING - Manuale - 1512.2_CSA_TTS
2. MAINTENANCE
SUPPOR
T CENTER
2.2.16. FAULT SIGNALLING CODES
CODE
FAULT
POSSIBLE CAUSE
SOLUTION
RESET
E01
FLAME FAILURE
NO FLAME LIGHT UP
MANUAL RESET
(PRESS THE RESET
‘
’ KEY).
NO GAS PRESSURE;
CHECK THE ADDUCTION NETWORK;
MASS OR BROKEN START-
UP ELECTRODE;
REPLACE IT;
GAS VALVE NOT OPENING;
REPLACE IT;
SLOW LIGHT UP TOO LOW
ADJUSTMENT;
ADJUST MINIMUM OR SLOW LIGHT UP;
VALVE INFEED PRESSURE
TOO HIGH (ONLY FOR GPL
BOILERS).
CHECK THE MAXIMUM ADJUSTMENT
PRESSURE
THE CONDENSATE
DISPOSAL SYSTEM IS
BLOCKED.
CHECK THE CONDENSATE
DISPOSAL SYSTEM AND EMPTY THE
CONDENSATE TRAP.
AIR PRESSURE SWITCH
TRIPPED
CHECK FLUE GAS
DUCTS, CHECK CABLE, REPLACE PART
WITH FLAME LIGHT UP
NEUTRAL AND PHASE
INVERTED POWER SUPPLY;
PROPERLY CONNECT THE POWER
SUPPLY;
IONIZATION ELECTRODE
BROKEN;
REPLACE IT;
IONIZATION ELECTRODE
CABLE DISCONNECTED.
CHECK THE WIRING.
ELECTRICAL CURRENT
PHASE-PHASE
IF THE TENSION MEASURES BETWEEN
NEUTRAL AND GROUND IS ALMOST
EQUAL TO THE ONE MEASURED
BETWEEN PHASE AND GROUND, YOU
HAVE TO INSTALL A PHASE-PHASE
TRANSFORMER KIT (COD. 88021LA)