1 Rac
c
o
rdi fumari_c
ond_AUSTRALIA_EN
26
R1K 50 RAIN - RAD - ING - Man.Inst. - 1901.1_SK.3_firm.L224C_AHS
1 Rac
c
o
rdi fumari_c
ond_AUSTRALIA_EN
1. INSTALLATION
INST
ALLER
1.1.18. FUME EXHAUST FITTINGS
WARNING
In order to ensure proper operation and
efficiency of the device you have to connect the boiler
fume exhaust fitting to the fume exhaust duct using
appropriate polypropylene flue fittings for condensing
boilers. It is recommended to install discharge
systems approved by Radiant.
› For all discharge ducts, with regard to the
fumes path, you should provide an uphill slope
(outwards) so as to favour the reflux of the
condensate towards the combustion chamber,
suitably realized to collect and drain acid
condensate.
› In order to discharge the fumes through a fumes
exhaust duct carefully follow the technical
standards in force.
› Suction and discharge systems, tailored to
individual installations, must be protected with
accessories that prevent the ingress of foreign
objects and atmospheric agents.
INSTALLATION REQUIREMENTS
For Australia – refer to AS/NZS 5601 and local authority for minimum clearances as illustrated below: