47
R1K 50 RAIN - RAD - ING - Man.Inst. - 1901.1_SK.3_firm.L224C_AHS
2 Dati tecnici_R1K 50 RAIN_AUSTRALIA_SK.3_EN
2. MAINTENANCE
SUPPOR
T
CENTRE
2.2.8. TECHNICAL DATA
Model
R1K 50 Rain
Maximum nominal heat capacity in heating circuit
MJ/h
198
Minimum nominal heat capacity in heating circuit
MJ/h
20
Useful thermal power - 60/80°C
kW
49,19
Minimum useful thermal power - 60/80°C
kW
4,83
Useful thermal power - 30/50°C
kW
53,40
Performance at 100% Pn - 60/80°C
%
98,37
Performance at 30% Pn - return 47°C
%
102,8
Performance at 30% Pn - return 30°C
%
108,83
Performance at 100% Pn - 30/50°C
%
106,8
Maximum combustion Performance
%
97,9
Fumes temperature at nominal heat capacity
°C
66,4
Fumes temperature at minimum heat capacity
°C
56,8
CO2 at nominal heat capacity - Natural Gas
%
9,3 - 9,1
CO2 at minimum heat capacity - Natural Gas
%
9 - 8,8
CO2 at nominal heat capacity - Universal LPG
%
10,3 - 10,1
CO2 at minimum heat capacity - Universal LPG
%
9,9 - 9,7
CO at nominal heat capacity
ppm
68
Fumes mass at nominal heat capacity
g/s
22,19
Fumes mass at minimum heat capacity
g/s
2,28
NOx class
class
6
Weighted Nox (0% O2) mg/kWh
mg/kWh
51
Heating circuit
Adjustable heating temperature
°C
30-80 / 25-45
Maximum operating temperature for heating circuit
°C
80
Maximum operating pressure for heating circuit
kPa
300
Minimum operating pressure for heating circuit
kPa
30
Dimensional characteristics
Width
mm
480
Depth
mm
600
Height
mm
910
Gross weight
Kg
54
Water connections
Flow
Ø
1 1/4”
Gas
Ø
3/4”
Return
Ø
1 1/4”
Fume exhaust fittings
Maximum electric fan pressure available
Pa
100
Minimum electric fan pressure available
Pa
30
Max discharge length Ø60 - Hor duct
m
5
Max discharge length Ø80 - Hor duct
m
25
Max discharge length Ø60 - Vert duct
m
5
Max discharge length Ø80 - Vert duct
m
25
Electrical specifications
Voltage-frequency V/Hz
240/50