1. INSTALLATION
INST
ALLER
KIT RAIN L – Ø 80 VERTICAL POLYPROPYLENE
PIPE. OUTSIDE INSTALLATION
It allows the flue discharge from the roof e and the
air input from the environment.
Suitable only for condensing boilers.
It allows the combustion flues discharge through
a polypropylene pipe and the air exhaust directly
from the hole situated on the room sealed chamber
plate protected by a metal net.
PLEASE SEE THE MAXIMUM DISCHARGE LENGTH
IN THE TABLE IN CHAPTER “TECHNICAL DATA”.
The maximum discharge length (or linear reference
length) can be calculated summing the length of the
linear tube and that equivalent to each additional
curve with respect to the first.
Subsequent addition of a curve is similar to adding
a linear length of tube according to the indications
below:
co-axial curve Ø80 to 90° = 1.5 m
co-axial curve Ø80 to 45° =
0.8
m
Ø80