37
R2KA 28 /20 - RAD - ING - Manuale - 1806.1_SK.2
2 T
a
bell
a p
a
r
a
metr
i_
MI
A
H
4
_
fir
m
.L
1
8
1
E
_
E
N
2. FIRST START-UP
SUPPOR
T
C
ENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P08
POST-CIRCULATION HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE PUMP
DURATION OF OPERATION DURING HEATING CYCLE, AFTER
THE MAIN BURNER TURNS OFF DUE TO THE ENVIRONMENT
THERMOSTAT.
0 - 90
VALUE EXPRESSED IN
MULTIPLES OF 5 SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P09
POST-CIRCULATION DOMESTIC / BOILER TIMING
THROUGH THIS PARAMETER YOU CAN SET THE PUMP
OPERATION DURATION ON THE DOMESTIC CIRCUIT, AFTER
THE TAP IS CLOSED.
0 - 90
VALUE EXPRESSED IN
MULTIPLES OF 5 SECONDS
(PRE-SET AT 24 X 5 = 120
SECONDS)
P10
DOMESTIC FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN DOMESTIC MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
45 - VALUE SET FOR
PARAMETER P11
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P11
DOMESTIC FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN DOMESTIC PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN DOMESTIC MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
VALUE SET FOR
PARAMETER P10
- 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P12
HEATING FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN HEATING MODE. [SEE CHAPTER ‘HEAT CAPACITY DIAGRAM
(KW) – ELECTRIC FAN FREQUENCY (HZ)’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
45 - VALUE SET FOR
PARAMETER P13
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)