MAINTENANCE INSTRUCTIONS
31
5. REGULATING THE BOILER
5.1 Parameters table
PARAMETER
N°
TYPE OF OPERATION
PARAMETER
VALUE
FUNCTION
P00
Selects the type of boiler
00-05
00 = Instantaneous boiler (w/dual
circuit exchanger)
01 = Instantaneous boiler
(w/secondary d.h.w plate exch.)
02 = Storage cylinder boiler
03 = Storage cylinder boiler with
Comfort function
04 = Instantaneous boiler
(w/secondary d.h.w plate exch.) with
Comfort function
05 = Only heating boiler
P01
Selects the type of gas supply
00
01
Natural gas
LPG
P02
Sets the central heating temperature
00
01
Standard (30-80°C)
Reduced (25-45°C)
P03
Water hammer prevention function
(Not applicable to only heating
boilers)
00
01
Off
On
P04
Central heating timer
00-90
Displayed in multiples of 5 seconds
(default value 36 x 5 = 180”)
P05
Central heating pump overrun timer
00-90
Displayed in multiples of 5 seconds
(default value 36 x 5 = 180”)
P06
D.H.W./ storage cylinder pump
overrun timer
(Not applicable to instantaneous
boilers w/dual circuit exchanger
and only heating boilers)
00-90
Displayed in multiples of 5 seconds
(default value 18 x 5 = 90”)
P07
Minimum central heating output
00 -
Max gas (P08)
Displayed in %
P08
Sets the maximum central heating
output and maximum gas pressure
Min gas (P07) - 99
Displayed in %
P09
Sets the ignition sequence
00-99
(default = 50)
Displayed in %
P10
D.H.W. priority function
(Not applicable to instantaneous
boilers w/dual circuit exchanger
and only heating boilers)
00
01
Off
On
P11
Legionella prevention function
(For storage boilers only)
00
01
Off
On
P12
Sets the climatic compensation curve
(w/outdoor temperature sensor only
installation)
00-30
See the graph in the parameter
setting explanation
P13
Central heating minimum Set Point
20 - 40
Displayed in °C
P14
Central heating maximum Set Point
40 -
90
Displayed in °C
P15
D.H.W maximum Set Point
(Not applicable to only heating
boilers)
45 - 75
Displayed in °C
P16
Post ventilation
(Not applicable for open chamber
models)
00 - 10
Displayed in minutes