REGULATION INSTRUCTIONS
35
PARAMETER
P14
–
IGNITION SEQUENCE SETTING
6. Use buttons ‘+’ and ‘-’ to modify the value of the parameter
between: min = 33 Hz; max = 203 Hz.
The default value is adjusted according to the output set in
parameter P00.
7. Press and release button ‘S’ to confirm. The parameter number
(P14) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
PARAMETER
P15
–
ZONE MANAGEMENT BOARD
ACTIVATION
6. If the system is fitted with zone valves, set the parameter at ‘01’. If
a remote control is installed, an extra interface board must be
installed to control the zone valves. Then set the parameter at ‘01’.
7. Press and release button ‘S’ to confirm. The parameter number
(P15) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER
P16
–
TELEPHONE
CONTROL
ACTIVATION
6. If a telephone interface is installed, enable the board by setting
parameter P16 at ‘01’.
7. Press and release button ‘S’ to confirm. The parameter number
(P16) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
N.B.: The connection of the telephone interface to contact TA of the
terminal board must be wired in parallel with the remote control
using two non-polarised conductors.
PARAMETER
P17
–
FAN
FREQUENCY
VALUE
DISPLAY
6. Use buttons ‘+’ and ‘-’ to modify the value of the parameter
between:
- 00 = Off;
- 01 = On.
If parameter value 01 is selected, during the boiler operation, the
display will show the fan frequency value for 10 min.
7. Press and release button ‘S’ to confirm. The parameter number
(P17) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
00
P 17
00
P 16
00
P 15
90
P 14