background image

INSTALLATION INSTRUCTIONS 

 

15

3.5 Water connections 

  In order to safeguard the heat exchanger and circulation 

pump,  especially  in  case  of  boiler  replacement,    it  is 
recommended that the system is hot-flushed to remove 
any impurities (especially oil and grease) from the pipes 
and radiators. 

   Make sure that the domestic water and central heating 

pipes  are  not  used  to  earth  the  electrical  system.  The 
pipes are totally unsuitable for this purpose. 

 

The 

Isolation  Valves  provided  must  be  installed 

on the heating and D.H.W circuits. This will facilitate all 
maintenance  and  service  operations  where  the  boiler 
needs to be drained. 

  To  prevent  vibration  and  noise  coming  from  the  system,  do 

not  use  pipes  of  reduced  diameter,  short  radius  elbows  or 
severe  reductions  in  the  cross  sections  of  the  water 
passages. 

  In  order  to  guarantee  the  reliability  of the  boiler  and  prevent 

permanent  damage  in  areas  with  very  high  water  inlet 
pressure a 2.5 bar pressure reducing valve should be fitted.

 

   To  facilitate  the  installation,  the  boiler  is  supplied  with  a 

hydraulic connection kit (see fig.2).  

Domestic hot water circuit 

  In order to prevent scaling and eventual damage to the D.H.W 

heat  exchanger,  the  mains  water  supply  must  not  have  a 
hardness  rating  of  more  than  17.5  °Ck.  It  is  nevert heless 
advisable  to  check  the  properties  of  the  water  supply  and 
install the appropriate treatment devices where necessary

The cold water supply pressure at the inlet to the boiler must be between 0.5 and 6 bar. 

In areas with higher water inlet pressure a pressure reducing valve must be fitted before the boiler.  

The  frequency  of  the  heat  exchanger  coil  cleaning  depends  on  the  hardness  of  the  mains  water  supply  and  the 
presence  of  residual  solids  or  impurities,  which  are  often  present  in  the  case  of  a  new  installation.  If  the 
characteristics  of  the  mains  water  supply  are  such  that  require  it  to  be  treated,  then  the  appropriate  treatment 
devices must be installed, while in the case of residues, an in-line filter should be sufficient. 

All  D.H.W.  circuits,  connections,  fittings,  etc.  should  be  fully  in  accordance  with  relevant  standards  and  water 
supply regulations.  

Guidance G17 to G24 and recommendations R17 to R24 of the Water Regulation Guide.  

Central heating circuit 

In order to prevent scaling or deposits in the primary heat exchanger, the mains supply water to the heating circuit 
must be treated according to the requirements of local standards.  

This treatment is indispensable in the case  where the circuit is frequently topped-up or  when the  system is often 
either partially or fully drained. 

The outlet connection of the boiler safety valve must be connected to a discharge pipe with a continuous fall from 
the boiler to outside. It must terminate in a safe position where any  water, possibly boiling, can discharge without 
causing a hazard. The manufacturer will not be held responsible for flooding or damage caused by the operation of 
the safety valve in the case of system overpressure. 

Condensate Drain  

The  condensate  drain  flexible  pipe  supplied  with  the  boiler  (conforming  to  UNI  EN  677  standard)  must  be 
connected to a proper condensate trap. The condensate discharge into the drainage system is allowed providing a 
condensate trap (siphon) is installed.  

Any  condensate  discharge  pipe  work  external  to  the  building  (or  in  an  unheated  part  of  it)  must  be  insulated  to 
protect against frost.  Before switching the boiler On, check the correct condensate discharge.  

HF

CWI

G

HWO

HR

49

78

70

80

102

31

1

0

5

Fig. 2 

Fig. 1 

Ø 15 mm

Ø 22 mm

HF

CWI

HR

HWO

Ø 22 mm

Ø  15 mm

Summary of Contents for RKR 24

Page 1: ...694 RKR 24_28_34 RAD ING MAN INST 1104A DIGITECH 2 REGNO UNITO EXTRAHEAT CBD Technical specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH Instruction Manual for model RKR 24 RKR 28 R...

Page 2: ......

Page 3: ...17 3 8 Gas connection 18 3 9 Electrical connections 19 3 10Flue connections 21 4 Commissioning the appliance authorised personnel 4 1 General warnings 27 4 2 Filling the system 28 4 3 Filling the con...

Page 4: ...ust be kept in a safe place and made available for future reference This Manual must be left along with the Benchmark commissioning booklet with the boiler as Regulation 29 of the HSC Gas safety insta...

Page 5: ...ordance with the requirements of current safety standards This fundamental safety requirement must be checked and verified In case of doubt have the electrical system checked by a qualified electricia...

Page 6: ...l unit that is easy to install and simple to operate In its simplicity the wall mounted appliance is equipped with all the appropriate accessories required to make it a fully independent boiler capabl...

Page 7: ...W flow rate at T 30K litr mn 11 1 13 4 16 D H W flow rate at T 35K litr mn 9 5 11 5 13 7 D H W flow rate at T 40K litr mn 8 3 10 1 12 D H W flow rate at T 50K litr mn 6 7 8 1 9 6 Dimensions Boiler cas...

Page 8: ...temperature 50 30 C Pn C 50 8 53 51 7 Flue gas temperature 80 60 C Pn C 71 65 73 3 Flue Mass 50 30 C Pn Pr Kg h 29 95 6 65 42 50 15 30 58 95 17 34 Flue Mass 80 60 C Pn Pr Kg h 28 32 6 49 39 32 15 08 5...

Page 9: ...63 285 131 S R HF CWI G HR HWO 65 280 65 730 15 25 730 70 49 78 80 102 31 410 285 2 2 Dimensions RKR 24 RKR 28 LEGEND HR HEATING RETURN mm 22 HF HEATING FLOW mm 22 G GAS mm 15 CWI COLD WATER INLET mm...

Page 10: ...10 132 730 HF CWI G HR HWO 70 49 78 80 102 31 310 730 111 5 187 111 5 48 5 313 48 5 105 RKR 34 LEGEND HR HEATING RETURN mm 22 HF HEATING FLOW mm 22 G GAS mm 15 CWI COLD WATER INLET mm 15 HWO HOT WATER...

Page 11: ...ELECTRODE 6 FAN 7 VENTURI 8 IGNITION TRANSFORMER 9 ELECTRONIC GAS VALVE 10 3 BAR PRESSURE RELIEF VALVE HTG CIRCUIT 11 AUTOMATIC AIR VENT VALVE 12 HEATING SAFETY THERMOSTAT 13 HEATING SENSOR 14 PUMP WI...

Page 12: ...14 PUMP WITH AIR VENT 15 WATER PRESSURE GAUGE 16 FLUE HOOD 17 SAFETY THERMO FUSE 18 EXPANSION VESSEL 19 D H W SENSOR 20 CONDENSATE TRAP 21 WATER PRESSURE SWITCH 22 AUTOMATIC BY PASS 23 CONDENSATE DRA...

Page 13: ...d speed Pump head at maximum speed III Flow l h Head kPa RKR 24 III II I Flow l h III Pump head at maximum speed Pump head at second speed II I Pump head at minimum speed Appliance Loss Head kPa RKR 2...

Page 14: ...mperature display When the boiler is switched off at the switch on the control panel the word OFF appears on the display The D H W and central heating frost protection system nevertheless remain enabl...

Page 15: ...d and 3 rd family gases BS 5449 Forced circulation hot water systems BS 6700 Installation of cold water supplies for domestic purposes 1st 2nd and 3 rd family gases BS 6798 Installation of gas fired h...

Page 16: ...are fully recyclable It is recommended that the packing material is only removed prior to installing the boiler The manufacturer will not be held responsible for damage caused by incorrect storage of...

Page 17: ...arances indicated in figure 1 are respected To make the installation easier the boiler is supplied with a template to enable the pipe connections to be positioned prior to fixing the appliance to the...

Page 18: ...ains water supply and the presence of residual solids or impurities which are often present in the case of a new installation If the characteristics of the mains water supply are such that require it...

Page 19: ...an automatic by pass is preferred Radiator valve Filling point DHW outlet Pressure reducing valve supplied Mains water inlet Static head of system Make up vessel Heating by pass if required Lockshield...

Page 20: ...insulated to protect against frost It is also recommended that the pipe diameter is increased to 32mm 8 If the boiler is fitted in an unheated location the entire condensate discharge pipe should be...

Page 21: ...must be a minimum of a 22 mm diameter pipe with an uninterrupted supply from meter to boiler and comply with current standards and regulations Check the internal and external seals of the gas supply s...

Page 22: ...nection to the mains electricity supply must be via a single pole switch with at least 3 millimetres gap between open contacts mounted upstream of the appliance Make sure that the positions of the liv...

Page 23: ...erminal board B as follows Connect the earth wire normally coloured green yellow to the terminal marked with the earth symbol Connect the neutral wire normally coloured blue to the terminal marked wit...

Page 24: ...minal is fitted less than 2m 6 6ft above a balcony above ground or above a flat roof to which people have access the terminal MUST be protected by a purpose designed guard Where the terminal is fitted...

Page 25: ...directly to the outside or can be connected to a suitable plume management system MAXIMUM FLUE LENGTH RKR 24 6 m RKR 28 6 m RKR 34 3 m The maximum flue length linear equivalent is obtained by totallin...

Page 26: ...ted directly to the outside or can be connected to a suitable plume management system MAXIMUM FLUE LENGTH RKR 24 12 m RKR 28 10 m RKR 34 8 m The maximum flue length linear equivalent is obtained by to...

Page 27: ...two separate 80 ducts MAXIMUM FLUE LENGTH 80 80 50 m 60 60 30 m The maximum flue length linear equivalent is obtained by totalling the length of linear pipe and the equivalent lengths of each bend fi...

Page 28: ...tion air while the 80 plastic inner duct discharges the exhaust fumes MAXIMUM FLUE LENGTH RKR 24 12 m RKR 28 10 m RKR 34 8 m The maximum flue length linear equivalent is obtained by totalling the leng...

Page 29: ...scharges the exhaust fumes MAXIMUM FLUE LENGTH RKR 24 6 m RKR 28 6 m RKR 34 3 m The maximum flue length linear equivalent is obtained by totalling the length of linear pipe and the equivalent lengths...

Page 30: ...nd earth wires are connected properly Also make sure that the earth connection is sound Check the seals on the gas supply pipe from the mains and make sure that the meter does not register any flow of...

Page 31: ...or the air evacuation process When water starts to flow out of the radiators close the air vents Use the pressure gauge M see fig 2 to check that the system pressure reaches 1 bar and that the code H2...

Page 32: ...illing operation is carried out as follows see fig 1 Remove plug T and fill the trap S three quarters full with water Replace plug T and connect the drainpipe P into a condensate discharge trap confor...

Page 33: ...tempting to light the boiler To reset the boiler Switch off switch 1 see 2 7 Control Panel and switch it back on again and repeat the lighting procedure With the boiler ignited if the system still emi...

Page 34: ...40 C P04 Heating output rising time 00 01 default 02 03 04 00 0sec 01 50 sec 02 100 sec 03 200 sec 04 400 sec P05 Water hammer prevention function 00 01 00 Off 01 On P06 D H W priority function 00 01...

Page 35: ...eping buttons and pressed Wait for P 00 to appear on the display 3 Release buttons and 4 Keep button S pressed and use button to select the parameter to modify 5 Release button S then re press and rel...

Page 36: ...will appear on the display 8 Switch off the appliance and switch it back on again to render the new parameter operative PARAMETER P02 SELECTS THE TYPE OF GAS 6 Use buttons and to modify the value of t...

Page 37: ...the parameter 00 off 01 on default 2 7 Press and release button S to confirm The parameter number P05 will appear on the display 8 Switch off the appliance and switch it back on again to render the ne...

Page 38: ...parameter within the prescribed limits 00 0 x 5 0 90 90 x 5 450 7 5 min The default value is 36 180 3 min 7 Press and release button S to confirm The parameter number P08 will appear on the display 8...

Page 39: ...the appliance and switch it back on again to render the new parameter operative PARAMETER P12 MINIMUM FAN SPEED SETTING CENTRAL HEATING 6 Use buttons and to modify the value of the parameter between...

Page 40: ...back on again to render the new parameter operative PARAMETER P16 TELEPHONE CONTROL ACTIVATION 6 If a telephone interface is installed enable the board by setting parameter P16 at 01 7 Press and rele...

Page 41: ...e di alimentazione mbar 20 30 37 Consumi 15 C 1013 mbar m 3 h 1 90 Consumi 15 C 1013 mbar kg h 1 42 1 4 Heating Power kW Fan frequency Hz diagram G 31 G 30 G20 CO2 Values Gas type CO2 Natural gas G20...

Page 42: ...Pressione nominale di alimentazione mbar 20 30 37 Consumi 15 C 1013 mbar m3 h 2 65 Consumi 15 C 1013 mbar kg h 1 97 1 94 Heating Power kW Fan frequency Hz diagram G20 G30 G31 CO2 Values Gas type CO2...

Page 43: ...as G 31 10 3 Table no 2 Frequency Gas type Minimum Hz Maximum Hz Natural gas G20 55 164 Liquid Butan Gas G 30 52 155 Liquid Propane Gas G 31 52 155 Table no 3 Gas data table NATURAL GAS G20 LIQUID BUT...

Page 44: ...Conversion is performed as follows Select the new gas type by changing parameter no P02 see Parameters table 5 2 Unscrew the aluminium plug and insert the analyser in the exhaust sampling point PF see...

Page 45: ...in line with section Commissioning the boiler Remove and clean any oxidation from the burner Check that the seal of the room sealed chamber is undamaged and positioned correctly Check the primary hea...

Page 46: ...n up see fig 2 Left and right side panel Remove the fixing screws at the front and lower edge of the side panel to remove Grasp the bottom of the panel move it sideways and then upwards to remove it T...

Page 47: ...he radiators starting with the highest and moving down the system to the lowest When the system has been drained close the radiator breather valves and the drain valve If only the boiler needs to be d...

Page 48: ...r s components caused by non compliance with this instruction For all maintenance operations requiring removal of the boiler casing refer to the procedures described in paragraph 6 3 Accessing the boi...

Page 49: ...altering their positions with respect to the burner Clean the burner cylinder using a non metal brush and without damaging the ceramic fibre Check the integrity of the washer on the cover of the burn...

Page 50: ...erse order Fill the system with water and check for any leaks from the joints Part replacement Ignition and or flame detection electrodes see fig 2 Un Plug the electrode wires Slacken the fixing screw...

Page 51: ...MAINTENANCE INSTRUCTIONS 48 POSITIONING THE IGNITION ELECTRODE AND THE IONISATION ELECTRODE 1 1 7 5 0 5 3 5...

Page 52: ...es and fill the central heating circuit Then restart the appliance remembering to discharge any air that may be trapped in the system Gas valve see fig 2 Disconnect the joints and remove the gas pipe...

Page 53: ...nd remove the upper mounting bracket Remove the expansion vessel from the front of the boiler Replace the expansion vessel and re assemble the components following the above procedure in reverse order...

Page 54: ...verter valve and remove the cover Unscrew the two motor fixing screws and disconnect the wires Replace the motor and re assemble the components following the above procedure in reverse order Replace t...

Page 55: ...ove the modulation circuit board Replace the circuit board and re assemble the components following the above procedure in reverse order Switch on the electricity water and gas supplies and regulate t...

Page 56: ...turn pipes Remove the support brackets and pull out the heat exchanger Remove the regulation sensor from the old heat exchanger and refit it together with the two condensate drainpipes to the new one...

Page 57: ...brown brown light blue black brown light blue EV2 B EV1 A EV1 B EV2 A red light blue brown light blue brown Storage cylinder timer option for storage boilers only orange orange brown violet orange M1...

Page 58: ...the wires have been connected place plate A back to position and then the front case panel Connecting the outside temperature sensor Option Connect the wires to the terminal board inside the instrumen...

Page 59: ...roller wires When the wires have been connected place plate A back to position and then the front case panel Connecting a remote controller and the telephone control option Connect the wires to the te...

Page 60: ...tors governing the correction is reported in figure 1 The selection of the compensation curve is determined by the maximum delivery temperature Tm and the minimum outdoor temperature Te N B The y axis...

Page 61: ...ERMOSTAT k THERMOSTAT BROKEN l THERMOSTAT CABLE DISCONNECTED m THERMOSTAT LOCK OUT HIGH FLUE TEMPERATURE k REPLACE PART l CHECK THE ELECTRICAL CONNECTION m RESTART AND CHECK THE THERMOSTAT H20 NO WATE...

Page 62: ...5 minutes without any modulation The function is useful for combustion testing 08 Frost Protection Central heating circuit The function is activated when the heating sensor senses a temperature of 5 C...

Page 63: ...5 24046LA PUMP RSL 15 6 3 KU 27044LA CONDENSATE TRAP 35031LA IGNITION ELECTRODE 35032LA IONISTATION ELECTRODE 36068LA VENTURI MINIFOLD 36076LA ELECTRONIC GAS VALVE 37032LA FAN 40 00016 PRINTED CIRCUI...

Page 64: ......

Page 65: ......

Page 66: ...N PURPOSES ONLY AND ARE NOT BINDING THE COMPANY RESERVES THE RIGHT TO APPLY VARIATIONS WITHOUT PRIOR NOTIFICATION NEITHER WILL THE COMPANY BE HELD RESPONSIBLE FOR ANY INACCURACIES IN THIS HANDBOOK DER...

Reviews: