REGULATION INSTRUCTIONS
40
Technical data tables – RKR 34
Heating Power (kW) – Fan frequency (Hz) diagram
G20
G30 / G31
Table no.1 - CO
2
Values
Gas type
CO
2
%
Natural gas - G20
9.18
Liquid Butan Gas - G 30
10.3
Liquid Propane Gas - G 31
10.3
Table no.2 - Frequency
Gas type
Minimum (Hz)
Maximum (Hz)
Natural gas - G20
55
164
Liquid Butan Gas - G 30
52
155
Liquid Propane Gas - G 31
52
155
Table no.3 - Gas data table
NATURAL GAS
G20
LIQUID BUTANE GAS
G30
LIQUID PROPANE GAS
G31
ower Wobbe index (15°C;
1013 mbar)
MJ/Nm
3
45.67
80.58
70.69
Nominal Supply pressure
mbar
20
30
37
Consumption (15°C; 1013 mbar)
m
3
/h
3.6
-
-
Consumption (15°C; 1013 mbar)
kg/h
-
2.68
2.64