Parameters Th18, Th19, Th20, Th21, Th57, Th79 are found in the system menu
Thermostats menu and
should be adjusted to the needs of the user and the instruction above.
7.6.5 Configuration 10.3
Picture 23. Configuration 10.1
Work principle:
If the temperature in the boiler is higher than Th19 and if the difference between temperatures of two
probes is higher than Th57, the system heats the water in the buffer. P3 Pump is on if the temperature in
the buffer has reached Th59.
Anti-freeze and over temperature protection has been described above.
Example and recommended values:
Th18
=5°C,
Th19
=40°C,
Th21
=70°C,
Th57
=5°C,
Th59
=50°C.
S1 probe
Differential
P1 pump
T<5°C
T<40°C
T≥40°C
<5°C
OFF
≥5°C
ON
T≥70°C
ON
S2 probe
Modality
P3 pump
T<50°C
OFF
T≥50°C
Winter
ON
Summer
OFF
Wiring:
Connect the output for Buffer temperature sensor to the connector as shown in the diagram.
Connect the output for DHW Temperature sensor to the connector.
Connect the Pump P3 to the connector as shown in the diagram.
Connect the Electro valve to the connector as shown in the diagram.
Parameters:
They are factory-set.
The following parameters are found in the System menu, submenu Enables: