8.3 Maintenance of boiler
!
Daily maintenance of the boiler refers to the ejection of ash from the space
between the floor and pipe grate. If there is a large amount of ashes the fuel is not receiving a
large amount of air for combustion.Pay attention that the output channel of air from the fan
should always have a free passage without obstacles.
!
Within every seven days, the boiler should be thoroughly cleaned, by removing
the cover of the lining on the roof, as well as the outer and inner covers on the boiler, and
through the hole on the roof of boiler by means of cleaning equipment remove the tar and
grime from all surfaces of the boiler. Then take out the turbulators ( directing gas units ) and
clean them,too. Cleaning of fire box should be done through the upper and lower doors. Each
millimeter of tar on the inside surface of the boiler results in 5% less heat conduction.
!
It is particularly essential to regularly remove and clean the boiler
turbulators. Otherwise there is a situation that the turbulators are impossible to remove
from the boiler and the ashes have completely blocked them so that there is no passage
of flue gases.
Within every seven days clean the fan. The access to it by removing the metal protection that
is joined with a tin boiler insulation by elastic connection. Cleaning the fan should not be
done with water but mechanically, gently for the turbines, or pneumatically.