6.2.
Uplink Messages
The uplink message (sensor to web application) specific to the sensor is defined in following
table. The common uplink messages are not included in this section (see common messages
document).
Table 5 Uplink Message 0x14: Voltage Measurement Event
Byte
Description
0
Voltage Measurement Event Payload (see Voltage
Measurement Event Payload Definitions)
1-2
Voltage measurement in units of 10mV (range 0-3000)
The voltage measurement event is defined in the following table.
Table 6 Voltage Measurement Event Payload Definitions
Event Payload Description
0x00
Periodic report
0x01
Analog measurement has risen above upper threshold
0x02
Analog measurement has fallen below lower threshold
0x03
Report on change increase
0x04
Report on change decrease
The voltage measurement field in the uplink message is the analog measurement in
increments of 10mV with a range of 0-30V (0-3000).