background image

D2112/D2112E Installation Manual

Page  17

74-07111-000-D 1/96

© 1995 Radionics

Installation Guide for UL Applications

Introduction

The 

System Chart references components evaluated

and listed by Underwriters’ Laboratories for
compatibility with the panel. These components
meet the basic system requirements for the
applicable standard.

The 

System Wiring Diagram, Issue A  shows the

relationship between the panel and the accessory
components referred to in the 

System Chart. See the

installation and operation instructions for each
component for detailed instructions.

Optional Compatible Equipment

You can use UL listed components that do not
require evaluation for electrical compatibility in many
applications when installed according to the
manufacturer’s instructions.

Burglary Applications
You can use UL listed burglary alarm sensors that
do not require evaluation for electrical compatibility
in burglary applications. In some cases you must
use a UL listed Radionics interface module in
conjunction with the sensors. Consult the individual
component specification and installation documents
to determine suitability.

In burglary applications with one 7.0Ah, 12 VDC
battery the panel supports an auxiliary output of
350mA and an alarm (bell) output of 1.5A configured
as necessary. For additional loadings refer to the
Current Rating Chart for Standby Battery
Calculations.

For commercial burglary installations use a
maximum of 45 seconds of entry delay and a
maximum of 60 seconds of exit delay.

Test weekly:  UL Standard 1023 requires a weekly
test. Configure the User System Test to test the
battery. See 

User Configuration in the D2112/

D2112E Program Entry Guide for instructions.

Fire Applications
You can use UL listed fire initiating devices not
requiring electrical compatibility evaluation in any
application. For example: four-wire smoke detectors,
heat detectors, waterflow switches, and manual pull
stations are suitable fire initiating devices. Consult
the individual component specification and
installation documents to determine suitability.

When using four-wire smoke detectors, install a
suitable power supervision unit according to the
manufacturer’s instructions. Use the D133 Relay
Module to provide reset capability.

In fire applications with one 7.0Ah, 12 VDC battery
the panel supports an auxiliary output of 140mA and
a bell output of 720mA configured as necessary. For
additional loadings refer to the 

Current Rating Chart

for Standby Battery Calculations.

D2112 only:  Two-wire detectors must be electrically
compatible, and must be UL listed for use with the
D2112. See the Radionics Technogram 

Smoke

Detectors Compatible with the D2112 (73-07115-
000), or you may contact the detector manufacturer.

Test weekly:  Radionics recommends testing fire
and combined fire/burglary systems weekly.
Configure the User System Test to test the battery.
See 

User Configuration in the D2112/D2112E

Program Entry Guide for instructions.

For all Burglary applications the panel must be
programmed to send a supervisory signal to the
central station a minimum of once every 24 hours.

Do not set or program an automatic telephone dialer
or similar device to place a call to a police station
number that is not specifically assigned by that
station for such service.

Sounding Device
The sounding device shall operate for at least four
minutes before an automatic cutoff for Household
Burglary applications and at least 15 minutes for
Commercial Burglary applications.

For all Commercial Burglary applications the system
must be programmed to sound the audible device
every time the system is armed.

Enclosures
The D2103 enclosure is suitable for Household Fire
and Burglary applications only.

Enclosure tamper protection causing an immediate
alarm signal is required for all burglary applications.

Radionics offers three optional enclosures.

The D8103 enclosure is suitable for residential fire
and/or burglary installations and commercial
applications that do not require attack resistance or
approval by Factory Mutual. (See the System

 Chart

for acceptable applications.)

Summary of Contents for D2112

Page 1: ...D2112 D2112E Installation Manual Page 1 74 07111 000 D 1 96 1995 Radionics D2112 D2112E Control Communicator Installation Manual ...

Page 2: ... 7 Part 68 This equipment complies with Part 68 of FCC rules A label contains among other information the FCC registration number and ringer equivalence number REN Radionics registered the D2112 Control Communicator for connection to the public telephone network using an RJ38X or RJ31X jack Use the ringer equivalence number REN to determine the number of devices you can connect to the telephone li...

Page 3: ...iary Power Terminal 9 8 Testing and Replacing D2112E Fuses 9 External Relays Terminals 11 and 12 9 Connect the Points 10 Point 1 on the D2112 Only Terminals 13 and 14 10 Points 2 to 6 1 to 6 on D2112E Terminals 15 to 22 14 to 22 on D2112E 10 Points 7 and 8 on the D2112 Only Terminals 23 to 25 10 Program the Panel 12 Make the Telephone Connections 12 Power Up 12 Fill out the Point Chart 12 Unlock t...

Page 4: ...for the features you want to use Have the following additional documents handy as you read through the manual D2112 D2112E Program Record Sheet D2112 D2112E Program Entry Guide Security System User s Guide Introduction D2112 D2112E Control Communicator The Radionics D2112 and D2112E Control Communicators are shipped pre assembled from the factory You should receive the following parts with your D2...

Page 5: ...ng Run phone and sensor loop wiring away from AC conductors including the transformer wire Run keypad wiring away from AC and phone wiring EMI may also occur if you install the panel or run system wires near the following Computer network system Fluorescent fixtures Telephone cabling Ham radio transmitter site Heavy machinery and motors High voltage electrical equipment PBX telephone system Public...

Page 6: ...l locally from the keypad or the D5200 Releasing the Standby Switch from the closed position resets the panel The panel resets all its timers and counters and clears all buffers Transformer Terminals 1 and 2 Connect the transformer to terminals 1 and 2 on the panel before plugging it into the power source Use 18 AWG wire to connect the transformer to the panel Wire length should be kept as short a...

Page 7: ...ble report if terminal 6 is shorted to ground The D2112 sends a trouble report if terminal 6 is shorted to terminal 7 while the alarm output is activated Use this power for bells siren drivers piezo fire sounders electronic horns or other devices Available Power The panel combines power produced by the power supply with power from the secondary power source the battery to produce a total of 1 5A o...

Page 8: ... for your system Instructions for using stand alone power supplies are included Auxiliary Power Terminal 9 The continuous current draw for powered devices connected to terminal 9 including keypads must not exceed 350mA 140mA for fire and combined fire burglary systems Devices powered from this output must operate over a range of 10 2 VDC to 13 9 VDC You must use a minimum of five feet 22 AWG of wi...

Page 9: ...st the fuses use a Volt Ohm meter to follow these steps 1 Remove the fuse from the socket 2 Switch the meter to measure Ohms 3 Attach the meter leads to each side of the fuse 4 If the meter does not change when you connect the leads to the fuse the fuse is open blown Replace the blown fuse with a 5 mm x 20 mm 2 Amp Fast Blow fuse 5 If the meter measures 0 Ohms the fuse is closed normal and does no...

Page 10: ...er limited by the Authority Having Jurisdiction Burglar Devices Connect any number limited by available power of burglar devices to any point Do not combine fire detection and burglar devices Points 2 to 6 1 to 6 on D2112E Terminals 15 to 22 14 to 22 on D2112E Points 2 to 6 1 to 6 on D2112E are supervised non powered points The panel monitors sensor loops for normal shorted or open conditions Prog...

Page 11: ...r Loop suitable for Two Wire Smoke Detectors 6 8 K Ω Resistor required at End of Line For compatible smoke detectors see RPN 73 07115 000 Point 1 23 24 25 Point 7 Point 8 Unsupervised Points Open 2 4 13 9VDC Normal Closed 0 0 1 4VDC No End of Line Resistor D2112 15 16 17 20 21 22 19 18 Six Supervised Points Open 8 9 13 9VDC Normal 2 5 8 5VDC Short 0 0 2 0VDC 1 0 K Ω Resistor Required at End of Lin...

Page 12: ...112E Program Entry Guide for more information Use the program record sheet to gather the information you need to fill out the point chart D164 Phone Cord 25 26 27 28 29 T1 R R1 T Brown Green Red Gray To RJ31X Phone Jack Black Yellow Orange and Blue not used Figure 8 Phone Cord Figure 7 RJ31X Phone Jack R1 T1 1 2 3 4 5 6 7 8 R T PREMISES PHONE INCOMING TELCO LINE FULL MODULAR PHONE JACK RJ31X MODUL...

Page 13: ... report sent 13 0 VDC Battery restoral reports sent OK light on steady 13 9 VDC Battery float charged Test the System After finishing installation and programming make a complete functional test of the system Test the panel and all devices for proper operation Test after you first program the panel and after any subsequent programming session Clear after test To clear the alarm memory and report b...

Page 14: ...e connected to both the keypads common and the terminal 10 on the panel A stand alone power supply powering any device connected to the panel must also be connected to terminal 10 on the panel Do not connect the stand alone power supply to earth ground Telephone Dialing Format You can program the panel to use DTMF or pulse dialing See Phone Parameters in the D2112 D2112E Program Entry Guide Commun...

Page 15: ...ised with EOL resistors Open Loop Greater than 2 4 VDC but less than 13 9 VDC Normal Closed Loop Greater than 0 0 VDC but less than 1 4 VDC Point Response Time The panel scans point sensor loops every 500 milliseconds A point must be faulted for 2 scans before the panel initiates an alarm Short and restoral on circuit toggles arming state COMMON POINT INPUT End of Line Resistor Figure 13 Keyswitch...

Page 16: ...ystem Off Program the Keyswitch Keyswitch prompt to Easikey See the D2112 D2112E Program Entry Guide for instructions You must use a 12VDC option for the Easikey installation See the Easikey Installation and Operation Instructions Connect the Easikey door controller to the panel using a D133 Relay Module as shown in Figure 14 Make certain to connect the common for the Easikey s 12VDC power supply ...

Page 17: ...re initiating devices Consult the individual component specification and installation documents to determine suitability When using four wire smoke detectors install a suitable power supervision unit according to the manufacturer s instructions Use the D133 Relay Module to provide reset capability In fire applications with one 7 0Ah 12 VDC battery the panel supports an auxiliary output of 140mA an...

Page 18: ...culations to verify compliance The formula below includes a 10 contingency factor for depletion of battery capacity with age NFPA 72 Ampere Hour Calculation Formula Total B ___ x 24 Hrs Total C ___ x 067 Hrs 10 Contingency Total Ah required Total Ah requirements must not exceed Ah capacity of batteries Current Rating Chart for Standby Battery Calculations All currents are in milliamperes 1 ampere ...

Page 19: ...andard 2 Two or more required for this application Consult the appropriate standard 1 D2112 Only At least one detector required You can substitute other 2 wire detectors listed for use with the D2112 You could use the D262 with the D270 four wire base or other manufacturers four wire detectors You must use a listed power supervision relay with four wire detectors Listed bell siren housing required...

Page 20: ...rm P S Supervised with 6 8k Ω EOL Resistor P S P S P S P S P S P P Arming Station D202 Up to Four D2112E P S P S P S D126 Battery 12V 7Ah P P P P S 16 VAC 25 VA 60 HZ Transformer D1240 Battery 12V 4Ah D1625 S P P D133 Relay P D133 Relay P P P S P S P S P Listed Audible Signaling Device Rated At 10 2 TO 13 9 VDC Do NOT Use Vibrating Type Horns Required for Fire and Combined Fire Burglary Optional f...

Page 21: ...g in transformer D1625 Secondary Power Supply 12 VDC 4 0 Ah sealed lead acid rechargeable battery 7 0 Ah battery required for Fire and combined Fire Burglary systems Auxiliary Power Output 350mA maximum at 10 2 VDC to 13 9 VDC for devices powered at terminal 9 140mA for Fire and combined Fire Burglary systems Alarm Power Output 1 5 A maximum at 10 2 VDC to 13 9 VDC output Output may be steady or p...

Page 22: ...eypad Data Data for Keypads 9 Auxiliary Power Positive Supplies 350mA at 10 2 to 13 9 VDC for auxiliary power keypads and relay outputs 10 Common Common for Auxiliary Power and Relay Drivers 11 External Relay 1 Connect D133 Relay for Form C Dry Contact 12 External Relay 2 Connect D133 Relay for Form C Dry Contact 13 D2112 Positive Point 1 Not used on D2112E D2112 Positive power for Point 1 Switche...

Page 23: ...O I Menu Documents by Type Menu Documents by Product Menu Main Menu ...

Reviews: