D6500 Computer Interface Manual
74-05313-000-G 10/16/97
Page 27
© 1988-1997 Radionics, Inc.
D7112 and D9112B Messages Transmitted in BFSK
Automation Output
Signal
D6500 Internal/External Printer
D6500 Mode
SIA Mode
Notes
D9112B/D7112 Fire Messages – BFSK
Fire Alarm
dd/dd tt:tt ql ACCT aaa
FIRE
FR z
h1rrlssssssaaaasFssszt
<header>[#aaaa|NFAz]
2, 3, 9
Fire Trouble
dd/dd tt:tt ql ACCT aaa
TROUBLE
FR z
h1rrlssssssaaaaGsssszt
<header>[#aaaa|NFTz]
2, 3, 9
Fire Missing
dd/dd tt:tt ql ACCT aaa
TROUBLE
FR z
h1rrlssssssaaaaGsssszt
<header>[#aaaa|NFTz]
2, 3, 9
Fire Restoral
dd/dd tt:tt ql ACCT aaa
RESTORAL
FR z
h1rrlssssssaaaaHsssszt
<header>[#aaaa|NFRz]
2, 3, 9
after Alarm
Fire Restore
dd/dd tt:tt ql ACCT aaa
RESTORAL
FR z
h1rrlssssssaaaaHsssszt
<header>[#aaaa|NFRz]
2, 3, 9
after Trouble/Missing
Fire Walk Start
dd/dd tt:tt ql ACCT aaa
TROUBLE
ZN F
h1rrlssssssaaaasTsssFt
<header>[#aaaa|NBTF]
D9112
Fire Walk End
dd/dd tt:tt ql ACCT aaa
RESTORAL
ZN F
h1rrlssssssaaaasRsssFt
<header>[#aaaa|NURF]
D9112
D9112B/D7112 Alarm Messages – BFSK
Alarm
dd/dd tt:tt ql ACCT aaa
ALARM
ZN z
h1rrlssssssaaaasAssszt
<header>[#aaaa|NBAz]
2, 9
Duress
dd/dd tt:tt ql ACCT aaa
ALARM
ZN z
h1rrlssssssaaaasAssszt
<header>[#aaaa|NBAz]
2. D7112: z=0.
D9112: z= as programmed in
BFSK Duress Code
User Alarm 7
dd/dd tt:tt ql ACCT aaa
ALARM
ZN z
h1rrlssssssaaaasAssszt
<header>[#aaaa|NBAz]
2. D7112: z=7
D9112: z= as programmed for point (
Point Code Digit One =4)
User Alarm 9
dd/dd tt:tt ql ACCT aaa
ALARM
ZN z
h1rrlssssssaaaasAssszt
<header>[#aaaa|NBAz]
2. D7112: z=9
D9112: z= as programmed for point (
Point Code Digit One =5)
Cancel Alarm by Area
dd/dd tt:tt ql ACCT aaa
CANCEL REPORTh1rrlssssssaaaas\sssst
<header>[#aaaa|NOC]
2, 9
Trouble
dd/dd tt:tt ql ACCT aaa
TROUBLE
ZN z
h1rrlssssssaaaasTssszt
<header>[#aaaa|NBTz]
2, 9
Restoral
dd/dd tt:tt ql ACCT aaa
RESTORAL
ZN z
h1rrlssssssaaaasRssszt
<header>[#aaaa|NURz]
2, 9
Missing Alarm
dd/dd tt:tt ql ACCT aaa
ALARM
ZN z
h1rrlssssssaaaasAssszt
<header>[#aaaa|NBAz]
2, 9