background image

1997 Radionics                All rights reserved

The Radionics logo is a registered trademark of Radionics,

    1800 Abbott Street, Salinas, CA  93901, USA

74-07649-000-B        01/97
D9024/D10024 Installation

Page 5 of 17

B.  Circuit Connections

The D9024 and D10024 Fire Alarm Control Panels (FACP) are analog systems.  They exchange data

and may provide power to devices over two-wire circuits.  Radionics recommends shielded single pair

twisted cable wiring with a drain wire such as Atlas #218 or West Penn Wire/CDT #D293.
West Penn Wire/CDT #D293 has a nominal capacitance of 28 pf/ft between conductors.

Data Circuit Length

 is the distance over the circuit wire from the connection at the Control Module to

the most distant device and back to the Control Module.  Data Circuit Length must include the distance

to any device connected to the circuit in a “T” tap.

B.1.  Polling Circuit (D9067)

Detection devices in the analog system receive power and communicate with the control panel over

a two-wire circuit. The Digital Communications Protocol (DCP) resists interference from most types

of EMI and RF generated noise, and there are no special wiring requirements other than attention to

the wire gauge.  Under extremely noisy conditions, twisted pair wire is recommended to reduce

interference.  If EMI is a problem, use shielded cable, being careful to ground the drain wire to the

“E” terminal on the D10024M board.  See 

Figure 2

.

Polling  Circuit Length

Wire Gauge

Up to 4,000 ft.

18

4,000 - 7000 ft.

16

Table 1: Polling Circuit Length/wire Gauge

Note: The screw terminals will accept 14 AWG, but this will reduce the allowable length of the

circuit.

Any devices in the system that are not analog and are connected to the Digital Communications

Protocol (DCP) bus must be powered from a separate pair of conductors.
Each analog device is assigned a specific address by setting dip switches on that device.  Each

D9067 polling circuit can support up to 126 addresses.  It is not necessary to wire devices in any

particular order in a circuit.
The systems are expanded by adding D9067 Polling Circuit Modules to the Control Module.  The

D10024 has five expansion slots for polling circuits.  The D9024 has three.

+

CIRCUIT 

POLLING 

MODULE 

Shield Cable Drain

Earth Ground for

MODULE 

Data/power Common Out

Data/power Positive Out

Data/power Common Return

Data/power Positive Return

-

D9067

CIRCUIT 

POLLING 

D9067

 LOOP

+

-

E

-

2

+

-

E +

 LOOP

1

Figure 2:  Ground  Location on Control Module

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for D9024

Page 1: ...o provide reasonable protection against harmful interference in a commercial installation This equipment generates uses and can radiate radio frequency energy and if not installed in accordance with t...

Page 2: ...stallation 8 C 2 b D9067 Module Connection to the Control Module 9 C 2 c D9067 Module Connection to Class B Style 4 Circuit 9 C 2 d D9067 Module Connection to Class A Style 6 Circuit 10 C 2 e Shielded...

Page 3: ...Circuit Module Installation 8 Figure 7 Stacked Modules 9 Figure 8 D9067 Class B Style 4 Connection 9 Figure 9 D9067 Class A Style 6 Connection 10 Figure 10 D10024 Control Module Configuration 11 Figur...

Page 4: ...ircuits use types FPL FPL R or FPLP cable as applicable per NEC Article 760 A 1 Semi flush Mounting 1 Prepare an opening in the wall 20 x 20 x 5 1 2 2 Remove the knockouts asnecessary forwiring condui...

Page 5: ...nts other than attention to the wire gauge Under extremely noisy conditions twisted pair wire is recommended to reduce interference If EMI is a problem use shielded cable being careful to ground the d...

Page 6: ...ge B 3 Notification Appliance Indicating Device and Output Circuit Connections The D9024 and D10024 each has four power limited and supervised Class B Style W indicating circuits The terminal blocks f...

Page 7: ...ogrammed into the panel and are stored in the Central Processing Unit CPU to each analog device These levels can be altered through the front panel or PC programming Each device is programmed for Alar...

Page 8: ...as shown in Figure 6 COM 24V AUX 0V COM N C 24V N O N C N O AUX RELAYS RELAY 1 RELAY 2 OUT IN LOOP E 5 OUTPUTS SOUNDER 1 EARTH 2 DC DC E LOOP 4 E 3 LOOP E LOOP 2 E LOOP 1 D10024 Control Module 8 Wire...

Page 9: ...e Ribbon Socket 8 wire Ribbon Socket Figure 7 Stacked Modules C 2 c D9067 Module Connection to Class B Style 4 Circuit Connect the Data Power Positive wire of the polling circuit to the terminal of th...

Page 10: ...on Return Data Power Positive Out Data Power Common Out Figure 9 D9067 Class A Style 6 Connection C 3 D9051 RS 485 Bus Module The D9051 module is an RS 485 Network Expander It provides an isolated Cla...

Page 11: ...above Ports B C and D See Figure 10 COM 24V AUX 0V COM N C 24V N O N C N O AUXRELAYS RELAY1 RELAY2 LOOP E 5 OUTPUTS SOUNDER 1 EARTH 2 DC DC E LOOP 4 E 3 LOOP E LOOP 2 E LOOP 1 D10024 Control Module 8...

Page 12: ...e top of the D9051 Module Connect the A wire to the A terminal next to it If Shielded cable is used connect the drain wire s to the E terminal of the terminal block at the top of the Control Module Bo...

Page 13: ...hem in the same conduit and keep them apart inside the enclosure Connect the ground wire to the ground input middle terminal on 3 Amp fuse holder See Figure 13 The 120V neutral and line wires connect...

Page 14: ...300 A 300 mA x Qty 300 A 300 mA x Qty D327 320 A 320mA x Qty 320 A 320 mA x Qty 320 A 320 mA x Qty D329 280 A 280mA x Qty 280 A 280 mA x Qty 280 A 280 mA x Qty Other devices connected to the system n...

Page 15: ...No one to the negative terminal of battery N o two Connect the red wire lead from terminal 6 on the Power Supply to the positive terminal of battery No two Connect the black wire lead from terminal 7...

Page 16: ...LARM LED ALARM SILENCED LED AC POWER LED TROUBLE SILENCE KEY ALARM SILENCE KEY FIRE DRILL KEY 0 1 2 4 3 5 7 8 9 CHANGE System Trouble A N SHIFT 1 3 Alarm B O C P LED DISPLAY 7 Earth Fault 5 4 6 Troubl...

Page 17: ...el s internal buzzer will sound and the alphanumeric display will provide detailed information E 3 Alarm Conditions The red Alarm LED at the left of the indicator display flashes to indicate the syste...

Reviews: