Circuit overloading: When connecting the equipment to the AC circuits, the circuits
should be sized to safely provide all the amperage required by the all the
equipment in the rack-mounted enclosure. At a minimum, the supply circuit should
be capable of providing amperage equal to the sum of all the rating plate
amperages of the equipment contained in the rack/enclosure, plus 20-25% to
provide for inrush current peaks.
Reliable Earthing: Reliable earthing of rack mounted equipment should be
provided. Each piece of equipment within the rack/enclosure should be reliably
grounded to the branch ground. Care should be taken when using power strips
that the ground integrity through the strip is maintained.