background image

Page 13 of 22

IN052   Rev. K   0613

2.5.  Vent Line Installation

Use only 2”, 3” or 4” Schedule 40 PVC or equivalent pipe 

for vent line. Follow all applicable AARST, EPA, and/or 

State Standards for Radon or VOC venting.

1. 

Connect vent line to 2” socket elbow on the rear of the 

system (figure 9). Use PVC cement in a fashion that ensures 

no leakage will occur. Note: A rubber coupling permitting 

disconnection of the system from the vent line for future 

maintenance is provided beneath the cover.

2. 

The vent line must be mounted in a fashion that allows the 

system to exhaust above the level of the roof (Figure 10).

3. 

The vent must be pitched back towards the system to ensure 

that any condensation runs back into the unit. If an optional 

inline auxiliary fan is used, recommendations regarding 

pipe pitch in the fan installation instructions must be strictly 

adhered to.  

        

4. 

If an optional auxiliary fan is used then the fan must be 

wired to the system electrical box, connections as shown in 

the Electrical Schematic (Figure 8). This will ensure that the 

fan operates only when required by the system. The “red” 

lead is the live feed from the Aeration System to the Fan.

Warning: Do Not connect any of the Fan Leads to a separate power 

source. This will cause the Aeration System to Malfunction

5. 

Install weather cap on top of the vent line. This cap should 

not restrict air flow and must prevent rain, snow and other 

contaminants from entering the vent line.

Failure to install a proper vent line may cause 

contamination of the water, outgassing of 

contaminants into the building, limit system 

performance and/or cause the system to 

overflow. 

NOTE: The Manufacturer has found that vent lines less than 250 

equivalent linear feet do not cause a decrease in contaminant 

removal percentages. 90° Bend = 15 Equiv. Linear Ft ; 45° Bend = 

7 Equiv. Linear Ft. An inline auxiliary fan is recommended if the 

vent line exceeds 250 equivalent linear feet.

Figure 9 - Vent Line Connection

Figure 10 - Vent Line Installation

INSTALLATION INSTRUCTIONS

1

2

Vent 

connection

Summary of Contents for AIRaider EZ95

Page 1: ...AIRaider EZ95 Installation Instruction Manual RadonAway 3 Saber Way Ward Hill MA 01835 radonaway com IN052 Rev K 0613...

Page 2: ...Check 3 RETESTING 4 MAINTENANCE 4 1 Six Month Service recommended 4 2 Annual Service required 5 TROUBLE SHOOTING 6 ALARM SCHEMATIC 7 BLOWER BRUSH REPLACEMENT 8 EQUIPMENT SPECIFICATION LIMITED WARRANTY...

Page 3: ...afety 2 Installation site requirements 3 Inspection of System components 4 Qualified Technicians are necessary 5 Knowledge of all contaminants in the water 1 1 Safety Matters Safety is the most import...

Page 4: ...he system output the AIRaider EZ95 may run dry which will cause the pump installed integrally within the AIRaider EZ95 System to automatically shutdown To prevent outflow interruptions it is strongly...

Page 5: ...tem or the AIRaider EZ95 System Failure to remove other contaminants can reduce the effectiveness of the system and may result in system damage 1 3 Full Water Test A full Water Sample Analysis must be...

Page 6: ...5 System in accordance with the installation instructions Check your Local and State Code and Licensing requirements Failure to follow the instructions may lead to poor system performance and or possi...

Page 7: ...Raider EZ95 System are listed below Read all components of each step prior to beginning the actual installation 1 System Location 2 Readying the System for Installation 3 Plumbing Hook Up 4 Electrical...

Page 8: ...ing necessary this is typically in proximity to the well tank 2 Electrical Hook up Keep in mind the need for accessibility to a 20 Amp dedicated 120VAC power supply 3 Exhaust Line Venting The location...

Page 9: ...r level Pump float 3 Cable length tether to float normally open prevents pump dry running Vent On off float Float switch hose clamp Check valve behind pressure regulator Vent pipe hose clamps Push but...

Page 10: ...gned for use with a pressure tank The pressure tank bladder pressure should be set per the tank manufacturers recom mendations for a pressure switch setting of 37 psi 9 An outlet pipe must be installe...

Page 11: ...N C Blower Neon Lamp Push Button Thermostat Over Ride A B 1 2 C D E Blower Enclosure Electrical Enclosure Wiring NEZ SRT B G W B W W B B B B W W B B B R R R R W W W R RRG RRG B B W B W B B B B B B B B...

Page 12: ...tion 4 Ensure that the red lead provided for an optional auxiliary fan remains insulated if not used The red lead is the live feed from the Aeration System to the Fan Warning Do Not connect any of the...

Page 13: ...st be wired to the system electrical box connections as shown in the Electrical Schematic Figure 8 This will ensure that the fan operates only when required by the system The red lead is the live feed...

Page 14: ...ystem Start Up 1 Remove cover and lid and pour cup of chlorine into the AIRaider tank This will disinfect the system Secure the lid with the screws and washers provided 2 Check that all plumbing and e...

Page 15: ...given in Table 1 for the measured well pump output This is done by temporarily attaching a hose to the house connection of the bypass valve and adjusting the flow control valve to provide the correct...

Page 16: ...should be followed to maintain the AIRaider Check and or clean the blower air intake filter Check and or clean any filters or strainer installed on the inlet line to the AIRaider In installations with...

Page 17: ...f necessary Clean if necessary tank and diffusers of all mineral build up Chlorinate tank and lines by pouring cup of chlorine into the tank Check all control panel connections and electrical componen...

Page 18: ...not illuminated Check power switch in on position circuit breaker at panel in on position Check pump float switch for proper operation Check that the pump priming orifice rear left behind pump is not...

Page 19: ...Page 19 of 22 IN052 Rev K 0613 6 ALARM SCHEMATIC ALARM SCHEMATIC 1 2 3 4 5 6...

Page 20: ...ve the brush holder assembly from the motor 6 Insert the new brush holder assembly making certain that brass prongs engage the electrical socket and then replace the retaining screw 7 Repeat steps 4 6...

Page 21: ...0 VAC Buna N Seal Brass Valve Body NPT System Voltage 115V Electric Supply 20 Amp 115VAC Dedicated Circuit Recommended Flow Up to 7 GPM Radon Reduction Up to 95 Water Inlet Outlet Connections Sharkbit...

Page 22: ...AR PURPOSE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THERE IS NO WARRANTY OF MERCHANTABILITY ALL OTHER WARRANTIES EXPRESSED OR WRITTEN ARE NOT VALID In order to ob...

Reviews: