background image

Page 8 of 22

IN052   Rev. K   0613

2.2.   Preparing the System for Installation

1. 

Remove fasteners securing cover to tank and 

remove cover assembly.  (See Figure 3)

2. 

Remove lid

3. 

Remove any packing materials, manuals, bagged 

parts etc., from inside the system.

4. 

Check that the diffuser assembly is mounted in 

the elbow at the bottom of the front most pipe 

on the right of the tank and is secured via the 

mounting screw located      vertically thru elbow 

and horizontal diffuser pipe.

5. 

Ensure that pump float, is free to float over the 

diffuser bar.

6. 

Check that all liquid tight connectors on cables 

above the mounting plate are secure.

7. 

Check that all hose clamps on all floats and vent 

pipe are tight.

8. 

Verify float distances from mounting plate and 

cable lengths from tether to float are correct.

9. 

Mount the lid and lid gasket, do not secure with the fasteners provided at this time.   

 

 

10. 

Replace the cover assembly, do not secure with the fasteners provided at this time.

2.1.   System Location

When selecting the location for the AIRaider

 EZ

95

 System, six factors should be among those considered:

1. 

System Plumbing Hook-up. Find a location that will minimize the amount of plumbing necessary, this 

is typically in proximity to the well tank.

2. 

Electrical Hook-up. Keep in mind the need for accessibility to a 20 Amp dedicated 120VAC power 

supply.

3. 

Exhaust Line Venting. The location of the system must allow for outside venting of the system exhaust 

above the eave of the structure. The Manufacturer requires that the exhaust pipe pitch-back toward the 

system (see Section 2.5).

4. 

Remote Air Intake. If the system must be installed in an area with questionable air quality (i.e. furnace 

room, garage, crawlspace) then ducting from the air intake to a remote location having good air quali-

ty may be required.

5. 

System must be Level. The system should not be located on a significant slope as this may impede 

system performance and may cause system damage. 

6. 

Drain Location. The system is equipped with an overflow connection, it is recommended that this 

connection be directed to a drain or sump.

Place the system in the location acceptable to customer that maximizes the ease of installation. All Local and 

State codes as well as any applicable AARST, EPA and/or State Radon standards must be adhered to when 

locating the AIRaider

  (i.e. away from electrical panel, furnace, exits, etc.).

INSTALLATION INSTRUCTIONS

1

2

Cover assembly

Lid

Mounting plate
Spray nozzle
Pressure regulator
Pump bracket
Pump

Airguard

Diffuser assembly

Figure 3 - System Preparation

Summary of Contents for AIRaider EZ95

Page 1: ...AIRaider EZ95 Installation Instruction Manual RadonAway 3 Saber Way Ward Hill MA 01835 radonaway com IN052 Rev K 0613...

Page 2: ...Check 3 RETESTING 4 MAINTENANCE 4 1 Six Month Service recommended 4 2 Annual Service required 5 TROUBLE SHOOTING 6 ALARM SCHEMATIC 7 BLOWER BRUSH REPLACEMENT 8 EQUIPMENT SPECIFICATION LIMITED WARRANTY...

Page 3: ...afety 2 Installation site requirements 3 Inspection of System components 4 Qualified Technicians are necessary 5 Knowledge of all contaminants in the water 1 1 Safety Matters Safety is the most import...

Page 4: ...he system output the AIRaider EZ95 may run dry which will cause the pump installed integrally within the AIRaider EZ95 System to automatically shutdown To prevent outflow interruptions it is strongly...

Page 5: ...tem or the AIRaider EZ95 System Failure to remove other contaminants can reduce the effectiveness of the system and may result in system damage 1 3 Full Water Test A full Water Sample Analysis must be...

Page 6: ...5 System in accordance with the installation instructions Check your Local and State Code and Licensing requirements Failure to follow the instructions may lead to poor system performance and or possi...

Page 7: ...Raider EZ95 System are listed below Read all components of each step prior to beginning the actual installation 1 System Location 2 Readying the System for Installation 3 Plumbing Hook Up 4 Electrical...

Page 8: ...ing necessary this is typically in proximity to the well tank 2 Electrical Hook up Keep in mind the need for accessibility to a 20 Amp dedicated 120VAC power supply 3 Exhaust Line Venting The location...

Page 9: ...r level Pump float 3 Cable length tether to float normally open prevents pump dry running Vent On off float Float switch hose clamp Check valve behind pressure regulator Vent pipe hose clamps Push but...

Page 10: ...gned for use with a pressure tank The pressure tank bladder pressure should be set per the tank manufacturers recom mendations for a pressure switch setting of 37 psi 9 An outlet pipe must be installe...

Page 11: ...N C Blower Neon Lamp Push Button Thermostat Over Ride A B 1 2 C D E Blower Enclosure Electrical Enclosure Wiring NEZ SRT B G W B W W B B B B W W B B B R R R R W W W R RRG RRG B B W B W B B B B B B B B...

Page 12: ...tion 4 Ensure that the red lead provided for an optional auxiliary fan remains insulated if not used The red lead is the live feed from the Aeration System to the Fan Warning Do Not connect any of the...

Page 13: ...st be wired to the system electrical box connections as shown in the Electrical Schematic Figure 8 This will ensure that the fan operates only when required by the system The red lead is the live feed...

Page 14: ...ystem Start Up 1 Remove cover and lid and pour cup of chlorine into the AIRaider tank This will disinfect the system Secure the lid with the screws and washers provided 2 Check that all plumbing and e...

Page 15: ...given in Table 1 for the measured well pump output This is done by temporarily attaching a hose to the house connection of the bypass valve and adjusting the flow control valve to provide the correct...

Page 16: ...should be followed to maintain the AIRaider Check and or clean the blower air intake filter Check and or clean any filters or strainer installed on the inlet line to the AIRaider In installations with...

Page 17: ...f necessary Clean if necessary tank and diffusers of all mineral build up Chlorinate tank and lines by pouring cup of chlorine into the tank Check all control panel connections and electrical componen...

Page 18: ...not illuminated Check power switch in on position circuit breaker at panel in on position Check pump float switch for proper operation Check that the pump priming orifice rear left behind pump is not...

Page 19: ...Page 19 of 22 IN052 Rev K 0613 6 ALARM SCHEMATIC ALARM SCHEMATIC 1 2 3 4 5 6...

Page 20: ...ve the brush holder assembly from the motor 6 Insert the new brush holder assembly making certain that brass prongs engage the electrical socket and then replace the retaining screw 7 Repeat steps 4 6...

Page 21: ...0 VAC Buna N Seal Brass Valve Body NPT System Voltage 115V Electric Supply 20 Amp 115VAC Dedicated Circuit Recommended Flow Up to 7 GPM Radon Reduction Up to 95 Water Inlet Outlet Connections Sharkbit...

Page 22: ...AR PURPOSE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THERE IS NO WARRANTY OF MERCHANTABILITY ALL OTHER WARRANTIES EXPRESSED OR WRITTEN ARE NOT VALID In order to ob...

Reviews: