background image

IN006 Rev K 0417

4

3 Saber Way, Ward Hill, MA 01835   |   radonaway.com

For GP500 piping, the following table provides the minimum recommended pipe diameter and pitch under several 
system conditions.

*Typical GP500 operational flow rate is 25 - 90 CFM. (For more 
precision, determine flow rate by using the chart in the addendum.)

The GP500 incorporates a unique condensation drain system which actively 
pumps water back to the inlet piping for drainage to a slab hole.  It is required 
that the system piping provide a drop-off immediately at the inlet of the unit, 
as shown in Figure 1, to prevent reintrainment of condensation. If this is not 
possible the condensate drain tube may be extended to the point of drop off by 
slipping 5/16” ID tubing (available from RadonAway) over the drain tube.

An alternative condensation drain may be provided using the 3/8” NPT fitting 
on the bottom of the unit. The alternative drain system must account for Radon 
leakage as the drain is under positive pressure. If the unit is installed and 
electrical power is removed for extended periods of time the drain plug should be 
removed to allow water to drain from the unit.

IMPORTANT: Do not overtighten drain plug! Do not use a wrench or tighten beyond finger tight. Apply sealant to 
threads if required.

1.6 SYSTEM MONITOR & LABEL

A System Monitor, such as a manometer (P/N 50017) or audible alarm (P/N 28001-2) is required to notify the 
occupants of a fan system malfunction.  A System Label (P/N 15022) with instructions for contacting the installing 
contractor for service and also identifying the necessity for regular radon tests to be conducted by the building 
occupants, must be conspicuously placed where the occupants frequent and can see the label.

1.7 SLAB COVERAGE

The GP500 can provide coverage up to 1000+ sq. ft. per slab penetration.  This will, of course, depend on the 
sub-slab material in any particular installation and the diagnostic results.  In general, the tighter the sub-slab 
material, the smaller the area covered per penetration.  Additional suction points can be added as required. It is 
recommended that a small pit (5 to 10 gallons in size) be created below the slab at each suction hole.

1.8 ELECTRICAL WIRING

The GP500 plugs into a standard 115VAC outlet.  The use of a Ground Fault Interrupter circuit (GFI) is 
recommended for all installations and required for outdoor or wet installations.  All wiring must be performed in 
accordance with the National Fire Protection Association’s (NFPA)”National Electrical Code, Standard #70”-current 
edition for all commercial and industrial work, and state and local building codes. All wiring must be performed by 
a qualified and licensed electrician. Ensure that all exterior electrical boxes are outdoor rated and properly sealed to 
prevent water penetration into the box. A means, such as a weep hole, is recommended to drain the box.

1.9 SPEED CONTROLS

The use of electronic speed controls on the GP500 is NOT recommended.

Pipe

Diameter

Minimum Rise per 1 Foot of Run*

@ 25 CFM

@ 50 CFM

@ 100 CFM

4”

1/8”

1/4”

3/8”

3”

1/4”

3/8”

1 1/2”

RUN

RISE

Reviews: