background image

Page 3 of 8 

 

                          IN006 Rev G 

 

INSTALLATION INSTRUCTIONS   IN006 Rev G 

For 

DynaVac – General Series 

GP500    p/n 23003-1 

 

 

 

 
 

1.0  SYSTEM DESIGN CONSIDERATIONS 
 
1.1  INTRODUCTION 
 
The GP500 is intended for use by trained, professional Radon mitigators.  The 
purpose of this instruction is to provide additional guidance for the most 
effective use of the GP500.  This instruction should be considered as a supplement 
to EPA standard practices, state and local building codes and state regulations.  
In the event of a conflict, those codes, practices and regulations take precedence 
over this instruction. 
 
1.2  ENVIRONMENTALS 
 
The GP500 is designed to perform year-round in all but the harshest climates 
without additional concern for temperature or weather.  For installations in an 
area of severe cold weather, please contact RadonAway for assistance.  When not in 
operation, the GP500 should be stored in an area where the temperature is never 
less than 32 degrees F. or more than 100 degrees F. When the unit is turned off 
for extended periods of time the drain plug should be removed from the bottom of 
the unit. 
 
1.3  ACOUSTICS 
 
The GP500, when installed properly, operates with little or no noticeable noise to 
the building occupants.   Insure a solid mounting for the GP500 to avoid 
structure-borne vibration or noise. 
 
The velocity of the outgoing air must also be considered in the overall system 
design.  In some cases the "rushing" sound of the outlet air may be disturbing.  
In these instances, the use of a RadonAway Exhaust Muffler is recommended. 
 
1.4  GROUND WATER 
 
In the event that a temporary high water table results in water at or above slab 
level, water may be drawn into the riser pipes thus blocking air flow to the 
GP500.  The lack of cooling air may result in the GP500 cycling on and off as the 
internal temperature rises above the thermal cutoff and falls upon shutoff.  
Should this condition arise, the GP500 should be disconnected until the water 
recedes allowing for return to normal operation. 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for GP500

Page 1: ...Page 1 of 8 IN006 Rev G ...

Page 2: ...tion of this device may affect the combustion airflow needed for safe operation of fuel burning equipment Check for possible backdraft conditions on all combustion devices after installation 5 NOTICE There are no user serviceable parts located inside the fan unit Do NOT attempt to open Return unit to the factory for service 6 All wiring must be performed in accordance with the National Fire Protec...

Page 3: ...re the temperature is never less than 32 degrees F or more than 100 degrees F When the unit is turned off for extended periods of time the drain plug should be removed from the bottom of the unit 1 3 ACOUSTICS The GP500 when installed properly operates with little or no noticeable noise to the building occupants Insure a solid mounting for the GP500 to avoid structure borne vibration or noise The ...

Page 4: ... possible the condensate drain tube may be extended to the point of drop off by slipping 5 16 ID tubing available from RadonAway over the drain tube Figure 1 An alternative condensation drain may be provided using the 3 8 NPT fitting on the bottom of the unit The alternative drain system must account for Radon leakage as the drain is under positive pressure If the unit is installed and electrical ...

Page 5: ...TALLATION 2 1 A C POWER CONNECTION The GP500 requires an 18 gauge 3 wire SJ power cord RadonAway p n 27003 or equivalent For proper seal the cord diameter should be 5 16 To install 1 Prepare the power cord by stripping jacket and insulation as shown in Figure 2 2 Loosen sealing nut on electrical inlet by turning counterclockwise 3 Insert power cord and route as shown in Figure 3 4 Fasten power cor...

Page 6: ...crews provided Use nylon washers provided under the screw heads to prevent marring the finish 8 Complete piping run providing flexible couplings or other means of disconnect for servicing the unit Under certain circumstances a flexible pipe coupling RadonAway p n 79019 1 may ease installation This may be particularly true of gable side installations where the system piping runs perpendicular to th...

Page 7: ... following chart shows fan performance for the GP500 Typical CFM vs Static Suction WC 1 0 1 5 2 0 2 5 3 0 3 5 4 0 GP500 88 80 74 65 54 28 14 Power 70 130 watts varies with actual load conditions 115 VAC Inlet Outlet 3 PVC Mounting Brackets for vertical mount on bandjoist or sidewall 16 Mounting Centers Outdoor installations GP500 mounts flush to wall projecting only 4 with inlet duct passing throu...

Page 8: ... This Warranty is contingent on installation of the Fan in accordance with the instructions provided This Warranty does not apply where any repairs or alterations have been made or attempted by others or if the unit has been abused or misused Warranty does not include damage in shipment unless the damage is due to the negligence of RadonAway RadonAway is not responsible for installation removal or...

Reviews: