Page 5 of 8 

 

                          IN006 Rev G 

1.8  ELECTRICAL WIRING 
 
The GP500 plugs into a standard 115VAC outlet.  The use of a Ground Fault 
Interrupter circuit (GFI) is recommended for all installations and required for 
outdoor or wet installations.  All wiring must be performed in accordance with the 
National Fire Protection Association’s (NFPA)”National Electrical Code, Standard 
#70”-current edition for all commercial and industrial work, and state and local 
building codes. All wiring must be performed by a qualified and licensed 
electrician. 
 
1.9  SPEED CONTROLS 
 
The use of electronic speed controls on the GP500 is NOT recommended. 
 
 
2.0  INSTALLATION 
 
2.1  A.C. POWER CONNECTION 
 
The GP500 requires an 18 gauge, 3 wire SJ 
power cord, RadonAway p/n 27003 or equivalent.  
For proper seal, the cord diameter should be 
5/16".  To install: 
 
1) Prepare the power cord by stripping jacket 
and insulation as shown in Figure 2. 
 
2) Loosen sealing nut on electrical inlet by 
turning counterclockwise. 
 
3) Insert power cord and route as shown in 
Figure 3. 
 
4) Fasten power cord with cable clamp 
provided. 
                                                   
Figure 2 
5) IMPORTANT: Tighten sealing nut by turning 
clockwise.  Hand tight is adequate to provide 
seal. 
 
6) Connect wiring with wire nuts provided, 
observing proper connections: 
 
 

 

GP500 Wire 

Connection 

Green 

Ground 

Black 

AC Hot 

White 

AC Common 

 
7) Tape over wire and wire nut with 
electrical tape to seal out moisture. A 
rubber splicing tape or self-fusing silicone 
tape provide best moisture seal. 
 

 
 
 

Summary of Contents for GP500

Page 1: ...Page 1 of 8 IN006 Rev G ...

Page 2: ...tion of this device may affect the combustion airflow needed for safe operation of fuel burning equipment Check for possible backdraft conditions on all combustion devices after installation 5 NOTICE There are no user serviceable parts located inside the fan unit Do NOT attempt to open Return unit to the factory for service 6 All wiring must be performed in accordance with the National Fire Protec...

Page 3: ...re the temperature is never less than 32 degrees F or more than 100 degrees F When the unit is turned off for extended periods of time the drain plug should be removed from the bottom of the unit 1 3 ACOUSTICS The GP500 when installed properly operates with little or no noticeable noise to the building occupants Insure a solid mounting for the GP500 to avoid structure borne vibration or noise The ...

Page 4: ... possible the condensate drain tube may be extended to the point of drop off by slipping 5 16 ID tubing available from RadonAway over the drain tube Figure 1 An alternative condensation drain may be provided using the 3 8 NPT fitting on the bottom of the unit The alternative drain system must account for Radon leakage as the drain is under positive pressure If the unit is installed and electrical ...

Page 5: ...TALLATION 2 1 A C POWER CONNECTION The GP500 requires an 18 gauge 3 wire SJ power cord RadonAway p n 27003 or equivalent For proper seal the cord diameter should be 5 16 To install 1 Prepare the power cord by stripping jacket and insulation as shown in Figure 2 2 Loosen sealing nut on electrical inlet by turning counterclockwise 3 Insert power cord and route as shown in Figure 3 4 Fasten power cor...

Page 6: ...crews provided Use nylon washers provided under the screw heads to prevent marring the finish 8 Complete piping run providing flexible couplings or other means of disconnect for servicing the unit Under certain circumstances a flexible pipe coupling RadonAway p n 79019 1 may ease installation This may be particularly true of gable side installations where the system piping runs perpendicular to th...

Page 7: ... following chart shows fan performance for the GP500 Typical CFM vs Static Suction WC 1 0 1 5 2 0 2 5 3 0 3 5 4 0 GP500 88 80 74 65 54 28 14 Power 70 130 watts varies with actual load conditions 115 VAC Inlet Outlet 3 PVC Mounting Brackets for vertical mount on bandjoist or sidewall 16 Mounting Centers Outdoor installations GP500 mounts flush to wall projecting only 4 with inlet duct passing throu...

Page 8: ... This Warranty is contingent on installation of the Fan in accordance with the instructions provided This Warranty does not apply where any repairs or alterations have been made or attempted by others or if the unit has been abused or misused Warranty does not include damage in shipment unless the damage is due to the negligence of RadonAway RadonAway is not responsible for installation removal or...

Reviews: