8. [TI] Delay
[5s] Place empty
container
Pending for loading an empty container
for the second product
9. [CI] Input
condition
Input 1 – „/”
Input 1 has to take increasing tendency –
press function key confirming loading a
container
10. [T] Tare
Tare
Tarring the weighing platform no. 1
11. [DH] Dose
manually
0,2 kg [Sugar]
Manual weighing product “Sugar” to
obtain 0,2 kg mass
12. [TI] Delay
[5s] Unload
container with
product
Pending for unloading the container with
weighed product from the weighing
platform
13. [CI] Input
condition
Input 4 – „/”
Input 4 has to take increasing tendency –
press function key confirming unloading
a container from the weighing platform
14. [Z] Zero
Zero
Zeroing the weighing platform no. 1
15. [F] Set flags
Set signal flag 1
Setting the characteristic point of the
process, which is a condition for carrying
out part of the process on the second
weighing platform
16. [O] Outputs
Output 1 – „1”
Input 1 takes the high status (“1”) – signal
confirming carrying out the dosing
process on the weighing platform no. 1
is lit up
Platform 2:
Icon Step
Value
Description
1. [TI] Delay
[5s] Place empty
container
Pending for loading an empty container for
the third product (the first product on the 2
weighing platform)
2. [CI] Input
condition
Input 9 – „/”
Input 9 has to take increasing tendency –
press function key confirming loading a
container
3. [T] Tare
Tare
Tarring the weighing platform no. 2
4. [DH] Dose
manually
0,2 kg
[Seasoning]
Manual weighing product “Seasoning”
to obtain 0,2 kg mass
5. [TI] Delay
[5s] Unload
container with
product
Pending for unloading the container with
weighed product from the weighing platform
6. [CI] Input
condition
Input 12 – „/”
Input 12 has to take increasing tendency –
press function key confirming unloading a
container from the weighing platform
7. [Z] Zero
Zero
Zeroing the weighing platform no. 2
134