background image

 

889-3809-02 

Model 2018E Operations Manual Rev Apr 2020                Page 

1

 of 39 

Section 1

 

General Description 

This product manual is for people installing, operating, and maintaining the Reno A & E Model 2018E Conflict 
Monitor Unit (CMU).  We designed the Reno A & E Model 2018E monitor to meet or exceed the specifications in 
Chapter 3, Section 6, of the Caltrans Transportation Electrical Equipment Specifications (TEES) dated 08/16/02.  
Section 6 responds to the need for a monitor to accomplish the detection of, and response to, improper and 
conflicting signals and improper operating voltages in a Controller Assembly (CA).  This standard provides 
interchangeability between units of different manufacturers.  We developed this eighteen-channel monitor to allow 
users to take full advantage of all eighteen load switch positions in a Model 332 cabinet with three output files.  
This monitor is backward compatible with sixteen-channel monitors. 
 
The Model 2018E detects the presence of voltage on conflicting field connection terminals; it detects the absence 
of proper voltages on all of the signal field connection terminals of a channel, and it monitors for the presence of 
satisfactory operating voltages within the Controller Unit (CU) and the Model 2018E itself.  If any of these 
conditions exist or are out of tolerance for the minimum time defined in Chapter 3 Section 6 of the Caltrans 
Transportation Electrical Equipment Specifications (TEES) dated 08/16/02, the Output relay’s normally open 
contacts will transfer from the no fault state (relay energized) to the fault state (relay de-energized).  The closure of 
the Output relay contacts will cause the transfer of the traffic signals to Flashing Operation.  The fault is recorded 
by the Model 2018E and displayed on the appropriate LED indicators. 
 
The Model 2018E monitor can operate in one of several basic configurations: 
 

210 Monitor timings with 16 Channels using standard incandescent field display thresholds. 
210 Monitor timings with 18 Channels using standard incandescent field display thresholds. 
210 Monitor timings with 16 Channels using LED field display thresholds. 
210 Monitor timings with 18 Channels using LED field display thresholds. 
2010 Monitor timings with 16 Channels using standard incandescent field display thresholds. 
2010 Monitor timings with 18 Channels using standard incandescent field display thresholds. 
2010 Monitor timings with 16 Channels using LED field display thresholds. 
2010 Monitor timings with 18 Channels using LED field display thresholds. 
 

The differences between the 210 mode and the 2010 mode are: 
 

AC Power -

  In the 210 mode, the AC Line voltage is considered valid at >98V

RMS

  and invalid at 

<92V

RMS

.  In the 2010 mode, the AC Line voltage is considered valid at > 103V

RMS

  and invalid at 

<98V

RMS

. (Now a new Factory Option) 

 

Watchdog Timer Fault

 - In the 210 mode, a fault occurs if this input does not change states within 

1500 milliseconds of the last state change.  In the 2010 mode, a fault occurs if this input does not 
change states within 1000 milliseconds of the last state change. 
 

Stop Timing

  -  In the 210 mode, the Stop Timing output releases at the same time the Fault Relay 

returns to the no fault state.  In the 2010 mode, the Stop Timing output releases 250 milliseconds 
before the Fault Relay returns to the no fault state. 
 

Red Fail Timing

 - In the 210 mode, the Red Fail monitoring function will ignore faults of less than 

700 milliseconds duration and trigger on faults of more than 1000 milliseconds duration.  In the 2010 
mode the Red Fail monitoring function will ignore faults of less than 1200 milliseconds duration and 
activate on faults of more than 1500 milliseconds duration. 
 

Red Enable

 - In the 210 mode, a state change of the Red Enable input is recognized when it is in a 

state for at least 100 milliseconds.  In the 2010 mode, a state change of the Red Enable input is 
recognized when it is in a state for at least 400 milliseconds. 
 

The differences between the 16-channel and 18-channel mode are: 
 

The 16-channel mode of operation can only be selected by inserting a 16-channel diode card into the 
monitor.  In the 16-channel mode the monitor will only check the first 16 channels of the monitor for 
faults.  Channels 17 and 18 are checked to ensure that no green or yellow input is active while the 
monitor is in the 16-channel mode.  An active green or yellow on channel 17 or 18 will cause the 
monitor to transfer to the fault state with the 

PC AJAR

 and 

CONFLICT

  indications lit.  While the 

monitor is operating normally in the 16-channel mode the red, yellow and green indications for 
channel 17 and 18 will display the function inhibited indication. 
 
The 18-channel mode of operation can only be selected by inserting an 18-channel diode card into the 
monitor.  In the 18-channel mode the monitor will perform the same fault tests for channels 17 and 18 
as it would for the other 16 channels. 

Summary of Contents for 2018E

Page 1: ...ntains technical information for the Model 2018E Conflict Monitor pn 889 3809 02 Revision April 2020 Model 2018E Conflict Monitor Firmware Version 01 05 01 Operations Manual Caltrans TEES 2002 Conflic...

Page 2: ......

Page 3: ...BLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING ALL REGISTERED TRADEMARKS OF EBERLE DESIGN INC ARE UNDER COPYRIGHT MAINTENANCE NOTE IT IS AN E...

Page 4: ......

Page 5: ...emperature Sensor 7 2 4 7 Real Time Clock 7 2 4 8 Up Time Accumulator 7 2 4 9 Configuration Monitoring Beeping Monitor 7 2 4 10 Factory Settings 8 2 4 11 User Unit Information 8 2 5 Fault Monitoring 8...

Page 6: ...2 7 2 Monitor Reset Log 21 2 7 3 Configuration Event Log 21 2 7 4 Prior Faults Log 21 2 7 5 AC Line Log 21 2 7 6 Signal Sequence Log 21 2 8 Diagnostics 22 2 8 1 Memory 22 2 8 2 Microprocessor Monitor...

Page 7: ...ndicator 33 4 2 5 CONFLICT Indicator 33 4 2 6 RED FAIL Indicator 33 4 2 7 MULTI IND Indicator 33 4 2 8 YELLOW Indicator 33 4 2 9 PC AJAR Indicator 33 4 2 10 DIAG FAIL Indicator 33 4 2 11 COMM Indicato...

Page 8: ......

Page 9: ...escent field display thresholds 2010 Monitor timings with 16 Channels using LED field display thresholds 2010 Monitor timings with 18 Channels using LED field display thresholds The differences betwee...

Page 10: ...nection terminals in the Controller Assembly For the purpose of conflict determination a signal on any of the Green or Yellow inputs associated with a channel shall be considered as that channel being...

Page 11: ...nal input is measured approximately 13 000 times per second to provide an accurate true RMS root mean square AC voltage regardless of distortions in the waveform or changes in line frequency Both posi...

Page 12: ...on 2 to function Typical Connection Unterminated or Preemption circuitry 2 1 7 MC COIL INPUT The monitor provides an input to monitor the state of the Mercury Contactor MC Coil Rear Edge Connector Pin...

Page 13: ...less When operating in the 2010 mode prior to the monitor transferring the Output relay contacts from the Fault state to the No Fault state a transition state with a duration of 250 milliseconds occu...

Page 14: ...56 0 Hz or greater than 64 0 Hz The hysteresis from the OFF state to the ON state or vice versa is at least 3VRMS and the line frequency hysteresis is at least 1 0 Hz If the factory option for Low AC...

Page 15: ...Real Time Clock is initialized to local Pacific Standard Time when the unit is undergoing final test In addition the Daylight Saving Time user option is set to Off The Real Time Clock is preprogrammed...

Page 16: ...utput relay contacts to the fault condition activates the Stop Time output and illuminates the CONFLICT indicator on the front panel The Signal Sequence log and the Prior Faults log will record this f...

Page 17: ...f a Flashing Yellow Arrow channel the Yellow will still be used in the parent channel s red fail test regardless of the Yellow Disable jumper setting of the child channel 2010 Mode When the 2010 mode...

Page 18: ...en of the child channel will be included in the dual indication test for that channel If a Channel has an FYA setting with a yellow border for one of its child channels then the Yellow of the child ch...

Page 19: ...performed on all channels Test Preformed When a channel has a Green that turns off a conflicting channel cannot display a Green or Yellow for at least 2 7 seconds When each Green turns off a 2 7 seco...

Page 20: ...formed The Watchdog Timer input Rear Edge Connector Pin 22 is monitored A voltage of less than 4VDC is recognized as a low and a voltage greater than 12VDC is recognized as a high The input must chang...

Page 21: ...m the flashing state to the solid on state and not falsely trip Typical Use This feature is used to provide additional fault checking for Flashing Don t Walk displays on pedestrian channels Without th...

Page 22: ...ting with a green or yellow border for one of its child channels then the Yellow of the parent channel will be used for terminating the Yellow or Green of the child channel and will be checked for sho...

Page 23: ...Indication Monitoring The testing default for this feature should be disabled Operations Modified Dual Indication Monitoring When the Dual Enable switch is OFF for a channel and Green Yellow monitori...

Page 24: ...hort Yellow testing senses Greens Yellows and Walks as ON when their voltage is above 25VRMS and OFF when below 15VRMS Reds are ON when their voltage is above 70VRMS and OFF when below 50VRMS With LED...

Page 25: ...ADIAN FAST FLASH Configuration This is a factory option and cannot be changed by the user If this function is required but it is not active contact Reno A E Technical Support for assistance This featu...

Page 26: ...og When Log Field Changes is enabled the Signal Sequence log will change from recording the state and voltage on every input every 33 milliseconds to checking every 33 milliseconds to see if the state...

Page 27: ...annel 10 Green driving the flashing yellow arrow for the channel 7 left turn 2 6 4 3 FYA FOR CHANNELS 5 18 USE YELLOW DRIVERS FYA 5 18 USES YEL Configuration This feature is only effective if Flashing...

Page 28: ...e Yellow arrow parent channel Yellow used to terminate a flashing Yellow arrow and the Yellow of the conflicting child normally the opposing through Yellow ball will be ignored If the Yellow arrow is...

Page 29: ...te historical record of cabinet operation When the date and time are not available through Port 1 the monitor will use its internal Real Time Clock as a date time stamp for events 2 7 1 TIME CHANGE LO...

Page 30: ...ostic failure is not reset by a monitor Power Failure 2 8 1 MEMORY The monitor verifies all memory elements on power up or upon reset of a Diagnostics failure A failure of any of the memory tests will...

Page 31: ...mount of time DC Processor Timeout 6 0020h The DC processor did not respond to a request for data in the required amount of time Temperature Timeout 7 0040h The temperature sensor did not respond to a...

Page 32: ...AC VOLTAGE INPUTS Normal AC Power Thresholds Dropout 98VRMS Restore 103VRMS Low AC Power Thresholds Dropout 92VRMS Restore 98VRMS AC Line Frequency Dropout 56Hz or 64Hz Restore 57 5Hz and 62 5Hz MC C...

Page 33: ...l 350 ms FLASHING DON T WALK No Fault 1400 ms Respond 1600 ms Typical 1500 ms Flashing if state changes are 200 ms and 600 ms Typical 500 ms 2010 MODE OF OPERATION 24 VDC LOW No Fault 200 ms Detect 50...

Page 34: ...n I L Channel 7 Yellow I 11 Channel 14 Yellow I M Channel 3 Green I 12 Channel 3 Yellow I N Channel 16 Yellow I 13 Channel 9 Green I P Channel 17 Yellow I 14 Channel 17 Green I R Channel 10 Green I 15...

Page 35: ...O x x 5 Channel 13 Red I 4 Ground 6 Special Function 2 I 7 Channel 12 Red I 8 Special Function 1 I 9 Channel 10 Red I 10 Channel 11 Red I Ethernet Connector 11 Channel 9 Red I Pin Function 12 Channel...

Page 36: ...11 Green 12 Channel 13 Green N Channel 12 Green 13 Channel 14 Green P Channel 13 Green 14 Channel 15 Green R Channel 14 Green 15 Channel 16 Green S Channel 15 Green 16 Programming Card Ajar T Program...

Page 37: ...Mini USB Port Mini USB Port for communications with Laptop or Modem Field Status LEDs One LED for each field input All field status LEDs are latched if a fault occurs Field inputs that caused the fau...

Page 38: ...t flashing Don t Walk displays to not conflict with other greens or yellows at the intersection In order to use this feature the RaeComM software must be used to set the channels that this feature is...

Page 39: ...if the RED ENABLE input is not active The GY Dual Indication Monitoring enable can be used in conjunction with the DUAL ENABLE switches on the circuit board Channels that have their DUAL ENABLE switch...

Page 40: ...ed every 16 milliseconds by the monitor 4 2 1 FIELD STATUS INDICATORS There are 54 field status indicators one for each field input The display is logically organized into three columns and eighteen r...

Page 41: ...icate that a Short Yellow or Short Clearance fault has been detected on the field inputs See Section 2 5 4 for more information on a Short Yellow fault and Section 2 5 5 for more information on a Shor...

Page 42: ...ion change is identified the monitor will enter a configuration fault mode and the audible buzzer will start to beep at a one second rate This is an indication that a change to the current configurati...

Page 43: ...display mode While in the diagnostic display mode a short press of the front panel RESET pushbutton will advance to the next diagnostic display The diagnostic display sequence is Tap RESET to move be...

Page 44: ...Disable jumpers installed and Dual Indication is enabled for all channels 4 4 2 1 PERMISSIVE DISPLAYS The left display is the ID Display P1 The right display is the Data Display On the Data Display F...

Page 45: ...onitoring and the feature is enabled Flashing Yellow Arrow monitoring is enabled 2010 mode of operation is selected LED Thresholds are enabled Watchdog switch is set to enabled Flashing Yellow Arrow I...

Page 46: ...ally displaying the fault All LEDs except AC POWER and COM are displayed in the same state as they were when the prior fault occurred If the display reverts back to AC Line Voltage while trying to acc...

Page 47: ...th the monitor to be upgraded by clicking on IDENTIFY in the menu and observing that the monitor is correctly identified by the program 6 On the CONFIG menu choose UPGRADE FIRMWARE 7 On the Code Loade...

Reviews: