Duonet User Instructions
16
This function allows the disablement or enablement of programmed Network operation at
that control panel. The transmission and / or the receipt of signals may be disabled as
required. The control panel will indicate that disablements are present and a disablement
event will be recorded to log.
Disable / Enable: Default to all enabled
This function enables any device / action that may have been disabled, and all programmed
actions are reinstated. The control panel event log will indicate that all actions have been
reinstated.
Set Time and Date
This allows the time and date to be adjusted. These settings will need to be re-entered after
the complete removal of power, as the system will simply resume from the point that power
was removed.
Test Modes: Silent Test
The Silent Test function allows the selection of one or more detection-zones to operate in a
‘silent one-man walk test mode’. On triggering a device the device LED operates and the
event is recorded into the event log as a test activation, but the sounder does not sound and
the control panel does not show an alarm. After approximately 5 seconds the system will
reset the device, and another may be tested. The control panel event log will indicate that a
test mode has been selected.
Test Modes: Local Audible Test
The Local Audible Test function allows the selection of one or more detection-zones to
operate in a ‘one-man walk test mode with local sound’. On triggering a device the device
LED operates, the sounder within that device operates and the event is recorded into the
event log as a test activation, but the control panel does not show an alarm. After
approximately 5 seconds the system will reset the device, and another may be tested. The
control panel event log will indicate that a test mode has been selected.
Test Modes: Full System Test
The Full System Test function allows the entire system to operate in a simple one-man walk
test mode. On triggering a device the device LED operates and the event is recorded into the
event log, all the assigned sounders operate for 10 seconds and the control panel indicates
an alarm. After approximately 10 second the system will reset the device, and another may
be tested. The control panel event log will indicate that a test mode has been selected.
Please note, with the system test mode, only the sounders assigned to operate from that
device will sound, and any delays will still be present. i.e., if a delay of 2 minutes is present,
the system will have been reset before the sounders activate.
Test Modes: End all Tests
This function ends any test routine that may have been activated, and all programmed
actions are reinstated. The control panel event log will indicate that all actions have been
reinstated.
Summary of Contents for duonet
Page 21: ...Duonet User Instructions 21 Time Zone Device Event Action Initials...
Page 22: ...Duonet User Instructions 22 Time Zone Device Event Action Initials...
Page 23: ...Duonet User Instructions 23 Time Zone Device Event Action Initials...
Page 24: ...Duonet User Instructions 24 Time Zone Device Event Action Initials...
Page 25: ...Duonet User Instructions 25 Time Zone Device Event Action Initials...
Page 26: ...Duonet User Instructions 26 Time Zone Device Event Action Initials...
Page 27: ...Duonet User Instructions 27 Time Zone Device Event Action Initials...