Table 9 - Interconnect Cables
From
To Description
Sensor Terminal Board
Sensor board
12”, 25 conductor flat
ribbon cable
Sensor board
Main board
2”, 26 conductor flat ribbon
cable
Check that the cables are properly installed. If the cables check
out OK, the Sensor Terminal board may be defective. Contact the
factory for a replacement.
8.4
Rain Fall Sensor Verification Procedure
8.4.1 At the Evolution DX2 Controller
To insure that all cables are properly connected and that the Rain Fall
sensor is operational, the Rain Fall Sensor reading can be checked at the
Evolution DX2 Controller. Proceed to the Rain/Wind display using the
following menu sequences:
Step 1
Observe the Rain Sensor display and note the
measurement.
RAIN = 000.01/INCH
WIND = 000 MPH |
↑
|
F1 = Main Menu
F3 = Status
F2 = Measurements
F5 = Rain/Wind
Step 2
Remove the outer funnel-shaped rain collector from the
rain gauge (top half of bucket).
Step 3
Manually operate the internal dual reservoir mechanism
from one side to the other several times. Each time the
mechanism flips, a 0.01 inch count increase should be
displayed at the Evolution DX2 controller display.