ENGLISH RAIS - manual for GEO
7
Chimney
The chimney is the driving force which makes the stove function. In order for the stove to
perform satisfactorily the chimney height must be sufficient to ensure the correct draught
of 14 to 18 Pa so as to clear the products of combustion and prevent problems of smoke
emanating into the room when firing.
NOTE: A chimney height of not less than 4.5 metres measured vertically from the outlet
of the stove to the top of the chimney should be satisfactory. Alternatively the calculation
procedure given in BS 5854:1980 may be used as the basis for deciding whether a particular
chimney design will provide sufficient draught.
The outlet from the chimney should be above the roof of the building in accordance with the
provisions of Building Regulations Approved Document J.
If installation is into an existing chimney then it must be sound and have no cracks or other
faults which might allow fumes into the house. Older properties, especially, may have chim-
ney faults or the cross section may be too large i.e. more than 230 mm x 230 mm. Remedial
action should be taken, if required, seeking expert advice, if necessary. If it is found necessary
to line the chimney then a flue liner suitable for solid fuel must be used in accordance with
Building Regulations Approved Document J.
Any existing chimney must be clear of obstruction and have been swept clean immediately
before installation of the stove. If the stove is fitted in place of an open fire then the chimney
should be swept one month after installation to clear any soot falls which may have occurred
due to the difference in combustion between the stove and the open fire.
If there is no existing chimney then either a prefabricated block chimney in accordance with
Building Regulations Approved Document J or a twin walled insulated stainless steel flue to
BS 4543 can be used. These chimneys must be fitted in accordance with the manufacturer’s
instructions and Building Regulations.
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not
suitable for using for the complete chimney. The chimney and connecting fluepipe must
have a minimum diameter of 150 mm and its dimension should be not less than the size of
the outlet socket of the stove which is 150 mm in diameter. Any bend in the chimney or con-
necting fluepipe should not exceed 45°. 90°bends should not be used.
Combustible material should not be located where the heat dissipating through the walls
of fireplaces or flues could ignite it. Therefore when installing the stove in the presence of
combustible materials due account must be taken of the guidance on the separation of
combustible material given in Building Regulations Approved Document J and also in these
stove instructions.
Summary of Contents for GEO
Page 1: ...ENGLISH RAIS manual for GEO 1 U S E R M A N U A L RAIS GEO ...
Page 2: ...We cannot be held responsible for any misprints ...
Page 14: ...ENGLISH RAIS manual for GEO 14 Step 3 Step 2 ...
Page 15: ...ENGLISH RAIS manual for GEO 15 Step 5 Step 4 ...
Page 17: ...ENGLISH RAIS manual for GEO 17 Step 3 Step 2 ...
Page 18: ...ENGLISH RAIS manual for GEO 18 Step 5 Step 4 ...
Page 23: ...ENGLISH RAIS manual for GEO 23 ...
Page 35: ...ENGLISH RAIS manual for GEO 35 ...
Page 37: ...ENGLISH RAIS manual for GEO 37 ...
Page 38: ...ENGLISH RAIS manual for GEO 38 ...
Page 39: ...ENGLISH RAIS manual for GEO 39 ...
Page 40: ...RAIS A S Industrivej 20 DK 9900 Frederikshavn Danmark www rais dk ...