Raisecom
ISCOM6800 (A)Hardware Description
6 Electromechanical components
Raisecom Proprietary and Confidential
Copyright © Raisecom Technology Co., Ltd.
57
Table 6-4
Interfaces on the RPA2161-SI-220S54 panel
Interface
Type
Usage
Description
AC INPUT
SS-3B-6.3, 16 A/250 VAC
socket
Connect the external AC
power supply.
When being connected to the
external AC power supply, it
needs to be protected by a circuit
breaker.
LOAD
BTB760-00-04-01 terminal
block, connected to the OT
terminal by the M4 screw
Connect the power card
of the ISCOM6800.
When being connected with load,
it needs to be protected by a
circuit breaker.
BAT
BTB760-00-04-01 terminal
block, connected to the OT
terminal by the M4 screw
Connect the battery.
When being connected with the
battery, it needs to be protected
by a circuit breaker.
6.3.4 LEDs
Table 6-5 lists LEDs on the RPA2161-SI-220S54.
Table 6-5
LEDs on the RPA2161-SI-220S54
LED Quantity
Status
Description
RUN
2
Green
Module working LED
Fast blinking green (4 Hz): the module is working
properly.
Slow blinking green (1 Hz): the module is working
properly while the communication fails.
Off/Green: the module is working improperly.
ALM
2
Red
Alarm LED
Red: a fault is generated.
Off: no fault is generated.
6.3.5 Technical specifications
Table 6-6 lists technical specifications of the RPA2161-SI-220S54.
Table 6-6
Technical specifications of the RPA2161-SI-220S54
Parameter
Description
Dimensions
43.5 mm (Height) × 442.0 mm (Width) × 249.0 mm (Depth)
(without brackets)
43.5 mm(Height) × 482.6 mm(Width) × 249.0 mm(Depth)
(without brackets)
Weight
< 7 kg
Electrical feature 1
Input
200–240 VAC; 50/60Hz; 11 A MAX