Trouble Shooting Guide (cont.)
For testing the compressor, use a multimeter set at RX1 to test each of the three
terminal pins against each of the other two terminal pins. Each pair should show
continuity. Then, with the multimeter set at RX1000, place one probe against the
metal housing of the compressor (if necessary, scrape off a small amount of paint
to ensure contact with bare metal). Place the other probe on each of the three
terminals in turn. If any of the three terminals shows continuity with the housing,
the compressor is grounded. If the compressor fails either test, call for service at
888-944-7636. If the compressor passes the tests, reinstall the overload protector,
relay, terminal cover, and mechanical housing cover.