3.4
User interface
CMX 022 has 6 groups of DIP switches (S1-S6), whereas ControlMaster ®NXT 006 has operating digital
panel and large menu structure. The correct parameter settings for ControlMaster ®NXT 006 can be found in
chapter: "Commissioning".
CMX 022
ControlMaster ®NXT 006
Switch
Description
No:
Description
S1
Maximum driving frequency 1.
Drive status
S2
Minimum driving frequency
2.
Control selection
S3
Acceleration
and
deceleration ramp times
3.
Main menu
S4
Control mode and motor
type
4.
Back/reset button
S5
Motor current limit
5.
Navigation and confirmation (OK) buttons.
S6
Limit operation settings
3.5
EMC filter
CMX 022 has an external EMC filter package (KC310 / KC330), whereas ControlMaster NXT has an internal
EMC filter in the power supply. By default, the EMC level of the frequency converter is set to N by the
manufacturer.
If the mains network is non-grounded (IT-network), the ControlMaster ®NXT 006 frequency converter’s EMC
level must be changed to 0 by removing the filter capacitor disconnection screw.
Verify the type of electrical supply network from original electrical drawings.