Remote-Control Commands
R&S
®
SMBVB-K548
19
User Manual 1179.0922.02 ─ 01
Return values:
<ArbCfrOCrestFac> float
Range:
1 to 100
Increment: 0.01
*RST:
6
Example:
See
Usage:
Query only
Manual operation:
See
[:SOURce<hw>]:BB:ARBitrary:CFR:PFReq
<ArbCfrPassBFreq>
Sets the passband frequency, if
[:SOURce<hw>]:BB:ARBitrary:CFR:FILTer
is
set to
ENHanced
. Frequency components lower than the passband frequency are
passed through unfiltered.
Parameters:
<ArbCfrPassBFreq> float
Range:
0 to depends on the sample rate of the loaded file
Increment: 0.1
*RST:
250E6
Example:
See
Example "Setting up an Enhanced Filter"
Manual operation:
See
[:SOURce<hw>]:BB:ARBitrary:CFR:RCFactor?
Queries the resulting crest factor of the waveform after the calculations are completed.
The resulting crest factor is calculated as an average over the whole waveform, includ-
ing any idle periods that might be present in TDD waveforms.
Return values:
<ArbCfrResCreFac> float
Range:
1 to 100
Increment: 0.1
*RST:
6
Example:
See
Usage:
Query only
Manual operation:
See
[:SOURce<hw>]:BB:ARBitrary:CFR:SBANdwidth
<ArbCfrSignalBw>
[:SOURce<hw>]:BB:ARBitrary:CFR:FILTer
is set
to
SIMPle
.
The value of the signal bandwidth should not be higher than the channel spacing (
SOURce<hw>]:BB:ARBitrary:CFR:CSPacing
).