SECTION 15: R
EPLACEMENT
P
ARTS
53 of 59
15.8 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches are color coded for each pressure setting.
Carry out a start-up after working on or changing a pressure switch. See Page 29, Section 11.
15.9 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their
positions. Release the four mounting standoffs. Refit in reverse. Ensure correct location of ignition cable
and all other wiring.
15.10 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced
Carbon Monoxide Hazard
Use correct pressure switch specified for each
model.
Use of incorrect pressure switch or disabling
pressure switch circuit could cause unsafe
condition.
Failure to follow these instructions can result in
death or serious injury.
WARNING
MODEL
UHA
[T][M][X][S]
150 - 175
UHA
[T][M][X][S]
200 - 225
UHA
[T][M][X][S]
250
UHA
[T][M][X][S]
300
UHA
[T][M][X][S]
350
UHA
[T][M][X][S]
400
Pressure Switch
Kit P/N
90439803
90439808
90439812
90439811
90439805
90439811
Color Code
grey
orange
orange
grey
blue
grey
Set Point in. w.c.
0.41
0.79
0.18
0.72
0.55
0.72
Pressure Switch Snap
Ring P/N
90439850
90439850
90439850
90439850
90439850
90439850
MODEL
UHA[T][M][X][S] 150 - 175
UHA[T][M][X][S] 200- 250
UHA[T][M][X][S] 300 - 400
Axial Fan Guard
91901104
91901104
91901105
Axial Fan Motor
90600107
90600107
90600106
Axial Fan Blade
90709006
90709006
90709005
Summary of Contents for UHAM 150