UHA S
TANDARD
U
NIT
H
EATER
I
NSTALLATION
O
PERATION AND
S
ERVICE
M
ANUAL
56 of 59
16.2 General Technical Data Table
*Do not exceed the maximum length of flue stated or heater may not operate properly.
16.3 Technical Data Table
Model
UHA[T][M][X][S]
150
UHA[T][M][X][S]
175
UHA[T][M][X][S]
200
UHA[T][M][X][S]
225
UHA[T][M][X][S]
250
Full Load Amps @ 120 V
A
10.6
10.6
10.6
10.6
10.6
Air Volume
CFM
3500
3500
3716
3716
3716
Flue and Air Intake
Flue Intake Size
in (cm)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
Air Intake Size
in (cm)
4 (10)
4 (10)
4 (10)
4 (10)
4 (10)
*Maximum Straight
Flue/Air Intake
ft (m)
40 (1)
40 (1)
40 (1)
40 (1)
40 (1)
Weight (Net)
lbs
(kg)
217
(98.4)
237
(107.5)
255
(115.7)
265
(120.2)
270
(122.5)
Model
UHA[T][M][X][S]
150
UHA[T][M][X][S]
175
UHA[T][M][X][S]
200
UHA[T][M][X][S]
225
UHA[T][M][X][S]
250
Total Input High Fire
(Btu/h) x (1000)
150
175
200
225
250
Total Input Low Fire
(Btu/h) x (1000)
105
122.5
140
157.5
175
Total Output High Fire
(Btu/h) x (1000)
123
143.5
164
184.5
205
Total Output Low Fire
(Btu/h) x (1000)
86
100
115
129
143.5
Efficiency (Max Input)
%
82
82
82
82
82
Natural Gas Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.
Burner Pressure High Fire
in wc
3.0
3.0
3.2
3.4
3.45
Burner Pressure Low Fire
in wc
1.3
1.3
1.6
1.7
1.7
LPG / Propane Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.
Burner Pressure High Fire
in wc
11.1
11.2
9.5
11.1
11.6
Burner Pressure Low Fire
in wc
5.0
5.5
4.7
5.4
5.5
Summary of Contents for UHAM 150
Page 2: ......
Page 4: ......
Page 8: ......
Page 50: ...UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 42 of 59 14 1 General ...
Page 65: ...SECTION 16 SPECIFICATIONS 57 of 59 16 4 Dimension Data for Models UHA T M X S 300 400 ...
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......