SECTION 5: S
PECIFICATIONS
15 of 147
Table
8
: 2000-Series Selection Guide
*Temperature rise at this CFM is less than the maximum temperature rise. Heat output is based on heater operation in 100% outside
air mode.
**dBA is measured at 10' (3 m) from unducted discharge.
***Maximum Inlet Gas Pressure:ANSI - Compliant Manifold = 14 in wc (34.9 mbar)
FM and XL Compliant Manifold = 5 psi (344.7 mbar)
Airflow
CFM (m
3
/
h
)
Model
Motor HP at Noted
External Static
Pressure (in wc)
dBA** at Noted
External Static
Pressure (in wc)
Heat Output @ Max.
Temperature Rise
(Btu/h) x 1000
Minimum Inlet
Gas Pressure
in wc (mbar)***
Manifold Size
in NPT (mm)
0
0.25 0.50 0.75 1.00
0
0.50
1.00
NG
LPG
1,000 (1,700)
2005
2
2
2
2
2
62
66
70
97
76
7 (17.5)
0.75 (19)
2,000 (3,400)
2005
2
2
2
2
2
60
66
70
194
151
7 (17.5)
0.75 (19)
3,000 (5,100)
2005
3
3
3
3
3
60
65
70
292
227
7 (17.5)
0.75 (19)
4,000 (6,800)
2005
3
3
3
3
3
62
65
70
389*
302
7 (17.5)
0.75 (19)
4,000 (6,800)
2010
3
3
3
3
3
59
65
69
432
346
7 (17.5)
1.0 (25)
5,000 (8,500)
2010
3
3
3
3
3
58
63
68
540
432
7 (17.5)
1.0 (25)
6,000 (10,200)
2010
5
5
5
5
5
58
62
67
648
518
7 (17.5)
1.0 (25)
7,000 (11,400)
2010
5
5
5
5
5
59
62
66
756*
605
7 (17.5)
1.0 (25)
8,000 (13,600)
2010
5
5
5
5
5
60
63
66
800*
691
7 (17.5)
1.0 (25)
9,000 (15,300)
2010
7.5
7.5
7.5
7.5
7.5
61
64
67
800*
778
7 (17.5)
1.0 (25)
10,000 (17,000)
2010
7.5
7.5
7.5
7.5
7.5
62
65
68
800*
800
7 (17.5)
1.0 (25)
7,000 (11,900)
2010B
5
5
5
5
5
59
62
66
756
605
7 (17.5)
1.25 (32)
8,000 (13,600)
2010B
5
5
5
5
5
60
63
66
864
691
7 (17.5)
1.25 (32)
9,000 (15,300)
2010B
7.5
7.5
7.5
7.5
7.5
61
64
67
972
778
7 (17.5)
1.25 (32)
10,000 (17,000)
2010B
7.5
7.5
7.5
7.5
7.5
62
65
68
1,080
864
7 (17.5)
1.25 (32)
11,000 (18,700)
2010B
10
10
10
10
10
64
66
68
1,188
950
7 (17.5)
1.25 (32)
12,000 (20,400)
2010B
10
10
10
10
10
66
68
69
1,296
1,037
7 (17.5)
1.25 (32)
13,000 (22,100)
2010B
10
10
10
10
15
67
69
CF
1,404
1,123
7 (17.5)
1.25 (32)
14,000 (23,800)
2010B
10
10
15
15
15
69
CF
CF
1,512
1,210
7 (17.5)
1.25 (32)
12,000 (20,400)
2020
7.5
7.5
7.5
7.5
7.5
66
70
73
1,296
1,037
9 (22.5)
1.5 (38)
14,000 (23,800)
2020
10
10
10
10
10
69
70
73
1,512
1,210
9 (22.5)
1.5 (38)
16,000 (27,200)
2020
10
10
10
10
10
70
72
76
1,728
1,382
9 (22.5)
1.5 (38)
18,000 (30,600)
2020
15
15
15
15
15
70
74
77
1,944
1,555
9 (22.5)
1.5 (38)
20,000 (34,000)
2020
15
15
15
15
15
70
74
77
2,160
1,728
9 (22.5)
1.5 (38)
22,000 (37,400)
2020
20
20
20
20
20
71
74
77
2,376
1,901
9 (22.5)
1.5 (38)
25,000 (42,500)
2020
20
20
20
20
20
72
75
77
2,700
2,160
9 (22.5)
1.5 (38)
25,000 (42,500)
2030
15
15
15
15
15
70
72
74
2,700
2,160
11 (27.5)
2.0 (51)
27,500 (46,700)
2030
15
15
15
15
15
71
73
75
2,970
2,376
11 (27.5)
2.0 (51)
30,000 (51,000)
2030
20
20
20
25
25
73
75
76
3,240
2,592
11 (27.5)
2.0 (51)
32,500 (55,200)
2030
20
20
20
20
25
75
76
77
3,510
2,808
11 (27.5)
2.0 (51)
35,000 (59,500)
2030
20
25
25
25
25
77
77
79
3,780
3,024
11 (27.5)
2.0 (51)
37,500 (63,700)
2030
25
25
30
30
30
78
79
79
4,050
3,240
11 (27.5)
2.0 (51)
40,000 (68,000)
2030
30
30
30
30
30
80
CF
CF
4,320
3,456
11 (27.5)
2.0 (51)
Summary of Contents for 2005
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 31: ...SECTION 7 ROOF CURB 21 of 147 FIGURE 12 Curb Mounting Air Handler Roof Curb Fastening Detail...
Page 154: ...B SERIES INSTALLATION OPERATION AND SERVICE MANUAL 144 of 147...
Page 158: ......
Page 160: ......
Page 161: ......
Page 162: ......